Product Manual
Characteristic
Application
l
1 monitored digital input
l
Input lines are monitored for open line and short/open circuit (terminal resistors is
mandatory)
l
Microprocessor-controlled signal evaluation
l
Prevention of noise interference through intelligent analysis of input signals
l
LED display of input status
l
Automatic address setting, without encoder settings or Dip-switch
l
Power supply via FD18-BUS
l
Communication with controller via FD18-BUS(detection line)
l
Directly used in dry areas, Applicable in dusty and humid areas when installed in
FDCH221 housing
l
"Sticker Method" easy for commissioning
With the input a status can be monitored, the input can be configured by controller or
configuration tools as follows:
"Status" input or "Alarm" input
l
Lead monitoring for open line or open line and short circuit
l
When inputting status, according to different status of contact, can be set as
l
follows:
-
Normal mode: normally open input
-
Inverted mode: normally closed input
Building Technologies
Control Products and Systems

Advertisement

loading

Summary of Contents for Siemens FDCI181-1

  • Page 1 FDCI181-1 Input Module Product Manual Characteristic 1 monitored digital input Input lines are monitored for open line and short/open circuit (terminal resistors is mandatory) Microprocessor-controlled signal evaluation Prevention of noise interference through intelligent analysis of input signals LED display of input status...
  • Page 2 “Status” inputs and “Alarm” inputs “Alarm“ inputs trigger an alarm as soon as the input is activated. “Status“ inputs trigger a monitoring status change as soon as they are activated. Line monitoring and circuitry The input lines are monitored for open line or open/short line. To make these possible, resistors must be properly connected to the end of lines of the input (Fig.6).
  • Page 3 Fig. 6 Preparation Installation of module in FDCH221 housing Determine the type of installation: there are 2 types of installation for FDCI181-1 Input module: Caution! – Installation outside a switching cabinet or a control unit: Overheating of FDCI81-1 input module.
  • Page 4 Input module 0.080 kg FDCH221 S54312-F3-A1 100686595 Housing(IP65) 0.250 kg Beijing Siemens Cerberus Electronics Limited © Data and design subject to change without notice. No.1,Fengzhidonglu, Xibeiwang, HaiDian District, Beijing, 100094, China Tel: +10 6476 8806 Fax: +10 6476 8899 Doc No.