10
3.1.5 Specification
Items
Input Specification
Inputs Per Module
Indicators
Sensor Types
Excitation Current
Connection Method
Conversion Time
Data Format
Module Accuracy
Resolution of Data
Calibration
Diagnostic
General Specification
Power Dissipation
Isolation
4 Channels
4 Green Input Status LEDs
RTD Input Range
RTD Input
PT100, PT200, PT500, PT50
PT1000
JPT100, JPT200, JPT500, JPT50
JPT1000
NI100, NI200, NI500
NI1000
NI120
NI1000LG
Resistance Input
100mΩ/Bit
10mΩ/Bit
20mΩ/Bit
50mΩ/Bit
About 1mA
3-Wire
< 150ms, All Channel
16 Bits singed Integer (2' complement)
PT100, PT1000 Type Input Range
0.5℃ Full Scale @ 25℃ ambient
-
All Type Input Range
-
±0.1% Full Scale @ 25℃ ambient
±0.3% Full Scale @ -40 ~ 70℃ ambient
-
RTD Type: ±0.1℃ / F, Resistance Type: 100mΩ, 10mΩ, 20mΩ, 50mΩ
Not Required
Sensor open or range over, then conversion data = 0x8000 (-32768)
Max. 130mA @ 5Vdc
I/O to Logic: Photocoupler Isolation
Field power: Not Connected
HX-RIO3 Series
Input Range
-200~850℃
-200~350℃
-200~640℃
-200~350℃
-60~250℃
-60~180℃
-80~260℃
-50~120℃
Input Range
0~2000Ω
0~327Ω
0~620Ω
0~1200Ω