Data Value - Hitachi HX-RIO3 Series User Manual

Analog input module
Hide thumbs Also See for HX-RIO3 Series:
Table of Contents

Advertisement

28

3.3.8 Data Value

Type
Maximum Input Range
Type K
Type J
Type T
Type B
Type R
Type S
Type E
Type N
Type L
Type U
Type C
Type D
10uV
1uV
2uV
1℉
= 1.8
+ 32
Thermocouple Input Range
-270 ~ 1372 ℃
-210 ~ 1200 ℃
-270 ~ 400 ℃
30 ~ 1820 ℃
-50 ~ 1768 ℃
-50 ~ 1768 ℃
-270 ~ 1000 ℃
-270 ~1300 ℃
-200 ~ 900 ℃
-200 ~ 600 ℃
0 ~ 2310 ℃
0 ~ 2490 ℃
-81.0 ~ 81.0mV, 10uV / 1 Count
-32.7 ~ 32.7mV, 1uV / 1 Count
-65.5 ~ 65.5mV, 2uV / 1 Count
Recommended Input Range
-200 ~ 1200 ℃
-40 ~ 1100 ℃
-200 ~ 350 ℃
600 ~ 1700 ℃
0 ~ 1600 ℃
0 ~ 1600 ℃
-200 ~ 800 ℃
-200 ~ 1250 ℃
-100 ~ 850 ℃
-100 ~ 550 ℃
100 ~ 2100 ℃
100 ~ 2200 ℃
HX-RIO3 Series

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rio3-rtdRio3-tc

Table of Contents