INSITE PRO M COMPACT
SCU100
User manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB INSITE PRO M COMPACT SCU100

  • Page 1 INSITE PRO M COMPACT SCU100 User manual...
  • Page 3: Table Of Contents

    SCU100 INSITE PRO M COMPACT USER MANUAL Table of Contents 1.General Information....................5 1.1.Use and Storage of the manual ................5 1.2.Cleaning........................6 1.3.Installation to mains ....................6 1.4.Disconnection from mains or connections to mains ........6 1.5.Safety warnings .......................6 1.6.Disposal ........................6 1.7.Service and maintenance ..................6 1.8.Cyber Security disclaimer ..................7 2.System overview ....................8 2.1.Sub-distribution Control Unit SCU100 ..............8...
  • Page 4 SCU100 INSITE PRO M COMPACT USER MANUAL 9.Web User Interface ..................... 35 9.1.Structure .........................35 10.Web UI - Configuration ..................36 10.1.Devices ........................36 10.2.Groups ........................41 10.3.Tree view ......................42 10.4.Alarms ........................44 10.5.Automation ......................45 10.6.Export/Import ....................46 11.WebUI - Settings ....................47 11.1.Users ........................47 11.2.Email - FTP ......................
  • Page 5: General Information

    The information contained in this document is subject to change without notice and cannot be considered as an obligation by ABB Ltd. ABB Ltd. is not liable for any errors that may appear in this document. ABB Ltd. is not liable under any circumstances for any direct, indirect, special, incidental or consequential damage of any kind that may arise from using this document.
  • Page 6: Cleaning

    SCU100 INSITE PRO M COMPACT USER MANUAL 1.2.Cleaning Use a dry cloth. 1.3.Installation to mains Installation of device to mains shall include a switch or circuit breaker for the connection to mains. The switch or circuit breaker must be suitably located and easily reachable and must be marked as the disconnecting device for the device.
  • Page 7: Cyber Security Disclaimer

    ABB S.p.A. and its affiliates are not liable for damages and/ or losses related to such security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 8: System Overview

    SCU100 INSITE PRO M COMPACT USER MANUAL 2.System overview InSite pro M compact is a monitoring system which brings complete overview of the system performances and enables energy and asset management. The system consists of a Sub-distribution Control Unit (SCU100) and field devices connected to the control unit: energy and power meters, current sensors, digital input and output modules (I/O modules).
  • Page 9 SCU100 INSITE PRO M COMPACT USER MANUAL LEDs Two LEDs indicate respectively the status of the device and the one of the network. • LED Status Display Function Device is off Green on Device is ready Green flashing slowly Firmware is ready, Web server is loading Orange flashing slowly Firmware update ongoing Orange on...
  • Page 10: Current Sensors

    SCU100 INSITE PRO M COMPACT USER MANUAL 2.2.Current sensors CMS - Bus CMS - Bus interface interface Opening for the electrical conductor Push button Push button • Current sensors LED Status Display Function Sensor is online and in measurement mode. There is a feature in the configuration to switch off the LED of all the sensors after a specified time.
  • Page 11 SCU100 INSITE PRO M COMPACT USER MANUAL Sensors overview System Pro M, SMISSLINE S800 DIN rail Cable tie Mounting for all MCBs, for MCBs for fuse for all S800 universally universally method RCDs, (S200, SMISSLINE) holders devices with usable usable RCBOs with and RCBOs cage terminals...
  • Page 12: I/O Modules

    SCU100 INSITE PRO M COMPACT USER MANUAL 2.3.I/O modules The range of I/O modules is composed of: • Input Module with 4 inputs • Output Module with 4 outputs • Input and Output Module with 2 inputs and 2 outputs InSite-bus Interface Push button...
  • Page 13: Accessories

    SCU100 INSITE PRO M COMPACT USER MANUAL 2.4.Accessories Modbus RTU Adapter The Modbus RTU Adapter enables a simple connection from the 4th port of the SCU100 to the external ABB energy and power meters. Only meters equipped with Modbus RTU communication can be connected.
  • Page 14 SCU100 INSITE PRO M COMPACT USER MANUAL InSite Flat Cable The INS105 flat cable is a 4-pin cable for connecting multiple sensors and I/O modules to one control unit. Please take into account that possible cable length of the InSite flat cable depends on the number and shape of sensors, and on the number of I/O modules connected.
  • Page 15: Packaging Contents

    SCU100 INSITE PRO M COMPACT USER MANUAL 3.Packaging contents 3.1.Control unit Packaging contents Sub-distribution Control Unit SCU100 Modbus RTU Adapter: includes the device to be mounted on the right side of the control unit + segment of flat cable + connector Installation manual The following items are not included in the delivery product:...
  • Page 16: Technical Characteristics / Specifications

    SCU100 INSITE PRO M COMPACT USER MANUAL 4.Technical characteristics / specifications 4.1.Overall dimensions and technical data sub-distribution control unit 64,2 IEC61010-1 Supply voltage [VAC] 90-240 (L1-N) Voltage measurement range [VAC] 90-240 (L1-N, L2-N, L3-N) UL 508 / CSA C22.2 No. 14 Supply voltage [VAC] 80-277 (L1-N)
  • Page 17: Overall Dimensions And Technical Data I/O Modules

    SCU100 INSITE PRO M COMPACT USER MANUAL 4.2.Overall dimensions and technical data I/O modules 35,8 Input and Output Input module Output module module DM11 DM00 DM10 Number of digital channels 4 Input 4 Output 2 Input + 2 Output active input: 22-26 VDC active input: relay output:...
  • Page 18: Compatible Devices

    4.3.Compatible devices Devices compatible with I/O Modules include Molded Case Circuit Breakers (MCCBs), accessories of DIN- Rail protection devices, overvoltage Protection devices and meters pulse output. ABB ranges compatible with I/O Modules are: Molded Case Circuit Breaker Tmax XT Miniature Circuit Breakers...
  • Page 19: Main Functionalities And Measurements

    SCU100 INSITE PRO M COMPACT USER MANUAL 5.Main functionalities and measurements 5.1.Measurements Measurements in the system are given by connected devices and the SCU100 control unit itself. The principle of measurement for AC of the SCU100 control unit includes measurement on the mains and branches.
  • Page 20: Memory Architecture

    SCU100 INSITE PRO M COMPACT USER MANUAL Attention: Referring to the diagram in the figure aside, please note that N on the supply has to be connected in order to avoid damage of the device. Twisting the phase and neutral can damage the device. SCU100 L1/Supply N/Supply...
  • Page 21: Installation

    SCU100 INSITE PRO M COMPACT USER MANUAL 6.Installation Warranty Safe operation is ensured if assembly work has been carried out according to these user instructions. Furthermore, the instructions in the manual must be observed. Authorized Personnel Assembly, connection, and removal work should only be carried out by authorized and qualified personnel.
  • Page 22: Assembly Of Connectors, Current Sensors And I/O Modules

    To check if specific combinations of devices can be connected and to calculate maximum flat cable length, please refer to the interactive tool available at this link: https://search-ext.abb.com/library/Download. aspx?DocumentID=9AKK107680A1691&LanguageCode=en&DocumentPartId=&Action=Launch 1. Mark the desired placement of the connector with a pen: 2.
  • Page 23 • Mounting of System pro M compact and SMISSLINE Sensors Sensors fit to all ABB installation devices with twin terminals. Flat cable should not exert force on the sensor, otherwise measuring errors may occur.
  • Page 24 SCU100 INSITE PRO M COMPACT USER MANUAL • Mounting Sensors on DIN-Rails Sensors can be mounted on all 35-mm DIN-Rails (DIN50022). The cable should not exert force on the sensor, otherwise measuring errors may occur. 1. Snap in the bracket on the DIN-rail. 2.
  • Page 25 SCU100 INSITE PRO M COMPACT USER MANUAL Assembly of I/O modules • Assembly on 35mm DIN-Rail To assemble of the control unit, perform steps 1 and 2. The device can be mounted horizontally or vertically. To disconnect, perform steps 3, 4 and 5. Final connection Finally, connect the current sensors and the I/O modules to the control unit.
  • Page 26: Meters Connection

    SCU100 INSITE PRO M COMPACT USER MANUAL 6.3.Meters connection Connect up to 16 energy and/or power meters. Meters shall be connected in daisy chain configuration. A and B terminals of the Modbus Adapter are wired as follows SCU100 Modbus RTU Modbus adapter Port 4 adapter MA100...
  • Page 27: Wiring Diagram

    SCU100 INSITE PRO M COMPACT USER MANUAL 7.Wiring diagram The operations to carry out for the correct connection and wiring of the control unit and the I/O modules are described in this section. 7.1.Control unit Connection of SCU100 is based on the type of electric line available. The SCU100 includes an own power supply on L1-N.
  • Page 28 SCU100 INSITE PRO M COMPACT USER MANUAL Three phase plus neutral A B A B A B A B l3 l4/N Supply Attention: Please, referring to the diagram in the figure aside, notice that N on the supply has to be connected in order to avoid damage of the device.
  • Page 29 SCU100 INSITE PRO M COMPACT USER MANUAL I/O modules Connection of input and output channels to accessories and external devices is represented in the figure below. For sake of representation, connection to signal/auxiliary contacts and to loads is shown. InSite bus Input Output signal/auxilliary...
  • Page 30: Access To Control Unit

    DHCP access Hostname: Insite Note: If you change after initial commissioning for DHCP access Download latest software version here: https://search-ext.abb.com/library/Download.aspx?DocumentID=9AK- K107680A3552&LanguageCode=en&DocumentPartId=&Action=Launch For the first setup you have to use the direct LAN connection. Follow instructions under section “Direct LAN Connection”...
  • Page 31 SCU100 INSITE PRO M COMPACT USER MANUAL Accessing the Web UI via hostname Host name: insite, Port: 8000 To be added to the IP address to define the port number (e.g. 192.168.1.200:8000) to access your web browser. Defining the port number is important because without a port number access is not possible. In case of DHCP, the system administrator can read the IP address assigned to the SCU100 device by DHCP on the router.
  • Page 32 SCU100 INSITE PRO M COMPACT USER MANUAL → → Change adapter settings (on the left) Ethernet → → With right click select Properties double click Internet Protocol Version 4 (TCP/IPv4)
  • Page 33 SCU100 INSITE PRO M COMPACT USER MANUAL → Enter IP Address: 192.168.1.5 and Subnet Mask: 255.255.255.0 and confirm with OK. Make sure that the IP address on the LAN is not already taken. In case it is taken, adjustments are necessary.
  • Page 34: Control Unit Login

    SCU100 INSITE PRO M COMPACT USER MANUAL 8.2.Control unit login The web user interface is designed for use on browser-based devices. The recommended web browser is Google Chrome, other supported web browsers are Safari, Firefox, Opera, Internet Explorer. Start screen (login) Insert the IP address of the device in the browser address bar.
  • Page 35: Web User Interface

    SCU100 INSITE PRO M COMPACT USER MANUAL 9.Web User Interface Here the Web User Interface (WebUI) structure is shown. It is divided into two main areas: Operation and Settings area. On the one hand, the Operation area covers all pages where collected data is displayed and the system is controlled.
  • Page 36: Web Ui - Configuration

    SCU100 INSITE PRO M COMPACT USER MANUAL 10.Web UI - Configuration In order to start the configuration of the system, follow the instructions and indications detailed in this chapter, both “Configuration” and “Settings” menu. Safe shutdown: to make sure all settings are saved, it is recommended to carry out a safe shutdown before power off (Settings →...
  • Page 37 SCU100 INSITE PRO M COMPACT USER MANUAL Current Sensors The menu allows to have access to the information briefly listed below together with the buttons you can use. It is possible to use Selection Filter and Sort Function on Phase, Node and Group labels to find desired values.
  • Page 38 SCU100 INSITE PRO M COMPACT USER MANUAL Meters The menu allows to have access to the information briefly listed below together with the buttons you can use. It is possible to use Selection Filter and Sort Function on Node, Group, Type, Speed and Status labels to find desired values.
  • Page 39 SCU100 INSITE PRO M COMPACT USER MANUAL I/O Modules: Buttons Add and Create a new I/O Module ID and then assign it to the physical module assign new I/O by clicking the pushbutton on it (Note: Wait for confirmation before Module assigning the next sensor) Add new...
  • Page 40 SCU100 INSITE PRO M COMPACT USER MANUAL I/O Modules Definitions Module identification number (at this time it cannot be modified): it starts from 97 and the last digit indicates the channel number of the module It is automatically recognized when the module is added Module type and assigned.
  • Page 41: Groups

    SCU100 INSITE PRO M COMPACT USER MANUAL 10.2.Groups This page allows to create or remove groups of devices. By clicking on “Add new”, it is possible to create a new group by selecting the type of the devices. Once a group type has been selected, it is required to type the name of the group and add a description. For each group it is possible to associate one or more items.
  • Page 42: Tree View

    SCU100 INSITE PRO M COMPACT USER MANUAL 10.3.Tree view This page allows to replicate the structure of the existing electrical network by designing a tree-view scheme between nodes. The icon identifies a virtual single node or sub-node while the icon indicates a physical node.
  • Page 43 SCU100 INSITE PRO M COMPACT USER MANUAL To create a physical node just click on the setting icon, click “add node”, select a node type from the dropdown menu (Current sensors, Meters or I/O Modules) and add the available item. In the list are shown only devices already configured in “Configuration –...
  • Page 44: Alarms

    SCU100 INSITE PRO M COMPACT USER MANUAL 10.4.Alarms This page allows to set alarms. If an alarm occurs, it is shown in the “Analytics – Alarms log” section. An alarm can occur after exceeding the selected threshold values (cross-up), after measuring values lower than the selected threshold values (cross-down) for a determined period (time delay) or if a certain status changes (status change).
  • Page 45: Automation

    SCU100 INSITE PRO M COMPACT USER MANUAL 10.5.Automation This page allows to set automatic actions on selected devices if a specific configured event occurs. The automatic action can be set only for I/O Modules which have output channels already configured in “Configuration –...
  • Page 46: Export/Import

    SCU100 INSITE PRO M COMPACT USER MANUAL 10.6.Export/Import Export This page allows the export of complete settings of devices/groups/tree view and of historical values by checking the corresponding boxes and then clicking on “Download now”. Import: This page allows the import of settings and/or historical values. It is possible to choose to include or exclude devices/groups/tree view in the import.
  • Page 47: Webui - Settings

    SCU100 INSITE PRO M COMPACT USER MANUAL 11.WebUI - Settings 11.1.Users This page allows the “Administrator” user to add new users, as “Operator” or “Guest”, by clicking on “Add new”: only the Administrator can add other users’ profiles. In order to remove users already created, select the user to be deleted and click on “Remove selected”.
  • Page 48: Email - Ftp

    SCU100 INSITE PRO M COMPACT USER MANUAL 11.2.Email - FTP Email Settings for contact details. Email and FTP settings are needed in order to carry out email and FTP data export. Please make sure that no firewall will block the export. Make sure communication on SMTP port 587 or 465 (SSL) is allowed in your network.
  • Page 49: Communication

    SCU100 INSITE PRO M COMPACT USER MANUAL 11.3.Communication The following information have to be set to correctly have access to the user interface via IP: DHCP or static (Note: With DHCP you can find and define an IP address via the router by MAC address or IP Mode device/host name - insite) The fallback IP address is: 192.168.1.200:8000...
  • Page 50 SCU100 INSITE PRO M COMPACT USER MANUAL SNMP To enable version 3 mark the v.3 checkbox, enter UDP port number, password (at least 8 signs), security name and engine ID (at least 12 characters in hexadecimal format). Port number must be 161 or greater than 1024 (the same as for versions v.1/2c).
  • Page 51: Ssl Certificate

    SCU100 INSITE PRO M COMPACT USER MANUAL Ethernet/IP It is possible to enable Ethernet/IP protocol, download EDS files for PLC interfacing and files for Ethernet/IP Explorer software. A specific assembly can be defined adding multiple rows. 11.4.SSL certificate In this section it is possible to upload or generate a .pem file containing a private key and a public certificate in order to provide a secure connection via the web browser.
  • Page 52 SCU100 INSITE PRO M COMPACT USER MANUAL After configuration of domains/IP addresses table, please click the Generate button. When the generating process finishes, the web server reboots and due to a certificate change the page has to be reloaded manually. Follow the passages reported below to import the downloaded certificate into your web browser.
  • Page 53: General

    SCU100 INSITE PRO M COMPACT USER MANUAL 11.5.General Time • Time settings It is possible to synchronize the time to compare the time of the device and the one on the web browser. The synchronization is mandatory in order to correctly visualize and store data. By clicking on “Synchronize”...
  • Page 54 Using this menu you can update the firmware of the control unit. It is highly recommended to update the firmware to the latest version for security and functionality reasons. Please check the ABB website for current SW revision and to download the latest version of the firmware.
  • Page 55 SCU100 INSITE PRO M COMPACT USER MANUAL System In this section it is possible to carry out a system reset (to restart the device with the current settings), to restore the default settings and to carry out a safe shutdown. After any change in the settings we recommend you to do a safe shutdown.
  • Page 56: Webui - Monitor

    SCU100 INSITE PRO M COMPACT USER MANUAL 12.WebUI – Monitor 12.1.Real-time values Control Unit The “Real-time Values” section shows all measured values by control unit reporting the trend of the last 10s. If no graph is visible, it is necessary to synchronize the device time with the “Set time manually” button in the Settings –...
  • Page 57 SCU100 INSITE PRO M COMPACT USER MANUAL Current sensors Here it is possible to visualize “Real-time values” for the current sensors. Sensors have to be first assigned and configured (please refer to Configuration - Devices – Current sensors). In case of DC sensor measurement, please refer to “Configuration - Devices – Current sensors” and configure “Phase”...
  • Page 58 SCU100 INSITE PRO M COMPACT USER MANUAL I/O Modules Here it is possible to visualize “Real-time values” for each digital channel of the I/O module. “Real-time values” are “Status” and “Counter”. Only Administrator and Operator users are allowed to perform Reset of the counters...
  • Page 59: Webui - Analytics

    SCU100 INSITE PRO M COMPACT USER MANUAL 13.WebUI – Analytics 13.1.Historical values Here it is possible to visualize the “Historical values” of different measurements according to the category or group selected. Data resolution depends on the device and it binds the maximum time interval that can be shown. For I/O Modules it is possible to show pulses or “Counter”...
  • Page 60: Benchmark

    SCU100 INSITE PRO M COMPACT USER MANUAL 13.2.Benchmark Here it is possible to make comparisons between: • Measurements of two different devices in the same time interval (By device) • Measurements of one single device in two different time intervals (By period) As in “Historical values”...
  • Page 61: Data Export

    SCU100 INSITE PRO M COMPACT USER MANUAL 13.4.Data export In order to carry out data export via email and/or FTP, contact data for email and FTP server need to → be configured (see Settings Email, FTP). Here you can export and/or download measurement and/or historical alarms of the configured devices and edit data export settings: Settings Select type of data: “Total energy”, “Energy per phase”,...
  • Page 62: Webui - Control

    SCU100 INSITE PRO M COMPACT USER MANUAL 14.WebUI – Control 14.1.Control Here it is possible to change the status (open/close) of each single output port of the active modules. A confirmation message is shown before completing the action. Only Administrator user is allowed to perform control of devices...
  • Page 63: Modbus Tcp/Rtu Communication Interface

    SCU100 INSITE PRO M COMPACT USER MANUAL 15.Modbus TCP/RTU communication interface 15.1.Control unit mains and sensors readings Introducing MODBUS protocol The Modbus serial line protocol is a Master-Slaves protocol. This means that only one master and one or more slave nodes (max. 247) can be connected to the same serial bus. A Modbus communication is always initiated by the master and there is only one transaction at the same time.
  • Page 64 SCU100 INSITE PRO M COMPACT USER MANUAL Communication to CMS Physical Interface RS-485 To communicate with the CMS from an upper system, all devices (masters & slaves) must have the same data rate and data format. These settings are defined over the Web UI, as described in the dedicated chapter.
  • Page 65 SCU100 INSITE PRO M COMPACT USER MANUAL Error Codes Modbus protocol defines a common way of error reporting. Every request (read or write) sent in unicast mode is expected to return a value in packet of the same structure. In case of a message delivery error (not a CRC problem but a message execution problem), the generated response contains a function code with MSB (80h) set and a single byte representing the error code, called “exception code”.
  • Page 66 SCU100 INSITE PRO M COMPACT USER MANUAL Values with special meanings: Calculated branch power and energy values Special values (hex) Special values (dec) Meaning FFFF 7FF0 4'294'934'512 Data pending, acquisition in progress FFFF 7FF1 … FFFF 4'294'934'513 … 4'294'934'523 Reserved 7FFB FFFF 7FFC 4'294'934'524...
  • Page 67 SCU100 INSITE PRO M COMPACT USER MANUAL Show sensor “Write operation on this register starts or stops fast LED blinking of one specified sensor for diagnostic purpose.” Address Address Word Description Resolution Format 1 Access 2 (hex) (dec) (16-bit) and unit 3011 12'305 Show Sensor...
  • Page 68 SCU100 INSITE PRO M COMPACT USER MANUAL Polarity of sensors (for DC currents) These registers contain the configured nominal current value and the DC polarity information of each sensor with following bit format: 000P RRRR RRRR RRRR • R Reserved for future use •...
  • Page 69: Meters

    SCU100 INSITE PRO M COMPACT USER MANUAL 15.2.Meters Insite pro M allows to connect up to 16 meters with RS-485 interface. Supported are ABB M2M, M4M and EQ meters with Modbus RTU communication protocol. Each meter can be assigned to Modbus ID from 1 to 16.
  • Page 70: I/O Modules

    SCU100 INSITE PRO M COMPACT USER MANUAL If frequency for data refresh for Modbus, webserver or storage is 0, then data are requested/stored on demand (when changed). More details about each quantity is available in user manual for specific meter and can be accessed using meter address from meters tab in the Excel file.
  • Page 71 SCU100 INSITE PRO M COMPACT USER MANUAL Writable IO module IO module IO module External Modbus webserver storage Modbus...
  • Page 72: Simple Network Management Protocol - Snmp

    SCU100 INSITE PRO M COMPACT USER MANUAL 16.Simple Network Management Protocol – SNMP Reading of values The protocol is applicable for the following items: • Mains parameters • Calculated values • Measured branch current values If you need to record the values of a subsequent measurement, you have to use the SNMP protocol and the external storage system.
  • Page 73: Snmp Objects

    SCU100 INSITE PRO M COMPACT USER MANUAL Values with special meanings for calculated branch power and energy values (double word, 32bit) are reported below: Special values (hex) Special values Meaning (dec) 7FF0 32'752 Data pending, acquisition in progress 7FF1 … 7FFB 32'753 …...
  • Page 74 SCU100 INSITE PRO M COMPACT USER MANUAL Examples Some examples of usage on the Linux system using snmpget program from NET-SNMP package are presented below. The ‘#’ is the Linux command prompt. SNMPv1 # snmpget -v1 -c community_name 192.168.1.200:161 SNMPv2-MIB::sysUpTime.0 SNMPv2-MIB::sysUpTime.0 = Timeticks: (38471) 0:06:24.71 SNMPv2c # snmpwalk -v2c -c community_name 192.168.1.200:161 SNMPv2-MIB::system...
  • Page 75 SCU100 INSITE PRO M COMPACT USER MANUAL SNMPv3 # snmpget -v3 -e engine_id -u security_name -a MD5 -A password -x DES -X password -l authPriv 192.168.1.200:161 INSITE::tRMSsens1 INSITE::tRMSsens1 = INTEGER: 32767 # snmpgetnext -v3 -e engine_id -u security_name -a MD5 -A password -x DES -X password -l authPriv 192.168.1.200:161 INSITE::tRMSsens1 INSITE::tRMSsens2 = INTEGER: 32767 # snmpwalk -v3 -e engine_id -u security_name -a MD5 -A password -x DES -X password -l authPriv...
  • Page 76 SCU100 INSITE PRO M COMPACT USER MANUAL Modbus Standard TCP Port: 8001 Standard SNMP Port: 8002 Addr. Addr. Word Description Resolution Unit Format Access SNMP (hex) (dec) (16-bit) (1-bit value) Variable Name Ongoing measurement values: These registers contain the actual measured data. 0000 TRMS value of Sensor 1 0.01...
  • Page 77 SCU100 INSITE PRO M COMPACT USER MANUAL Addr. Addr. Word Description Resolution Unit Format Access SNMP (hex) (dec) (16-bit) (1-bit value) Variable Name Measured hold values: These registers contain the hold values captured at a given time during the execution of a “trigger hold measurement”...
  • Page 78 SCU100 INSITE PRO M COMPACT USER MANUAL Addr. Addr. Word Description Resolution Unit Format Access SNMP (hex) (dec) (16-bit) (1-bit value) Variable Name Branches 3200 Branch name of Sensor 1 letter string (03,10) 12'800 BranchNameSens1 3240 Branch name of Sensor 2 letter string (03,10) 12'864...
  • Page 79 SCU100 INSITE PRO M COMPACT USER MANUAL Addr. Addr. Word Description Resolution Unit Format Access SNMP (hex) (dec) (16-bit) (1-bit value) Variable Name Mains measurement registers 9002 36'866 2 PHASE VOLTAGE L1-N 0.01 unsigned R (03) 9004 36'868 2 PHASE VOLTAGE L2-N 0.01 unsigned R (03)
  • Page 80 SCU100 INSITE PRO M COMPACT USER MANUAL Addr. Addr. Word Description Resolution Unit Format Access SNMP Variable (hex) (dec) (16-bit) (1-bit value) Name Mains measurement registers 90AE 37'038 ACTIVE ENERGY L1 100Wh unsigned R (03) whL1-100 90B0 37'040 ACTIVE ENERGY L2 100Wh unsigned R (03) whL2-100 90B2...
  • Page 81 SCU100 INSITE PRO M COMPACT USER MANUAL These registers contain the general overview of the system, from numbers of channels and connected devices to SCU100 configuration. Addr. Addr. Word Slave Category Description Unit Format Access (hex) (dec) (16-bit) Modbus FBDE 6447 8 1 System view Nr of connected meters Unsigned...
  • Page 82 SCU100 INSITE PRO M COMPACT USER MANUAL Addr. Addr. Word Slave Category Description Unit Format Access EQ Meter (hex) (dec) (16-bit) Modbus Resolution Res. Res. Energies 9342 37698 4 phases Reactive net L1 kvarh Signed 0.01 0.01 - Energies 9346 37702 4 phases Reactive net L2 kvarh Signed...
  • Page 83 SCU100 INSITE PRO M COMPACT USER MANUAL Addr. Addr. Word Slave Category Description Unit Format Access EQ Meter (hex) (dec) (16-bit) Modbus Resolution Res. Res. Voltage harmonics 939F 37791 Harmonics THD L1-L3 Unsigned Voltage harmonics 93A0 37792 3rd L1-L2 Unsigned Harmonics Voltage harmonics 93A1...
  • Page 84 SCU100 INSITE PRO M COMPACT USER MANUAL Addr. Addr. Word Slave Category Description Unit Format Access EQ Meter (hex) (dec) (16-bit) Modbus Resolution Res. Res. AVER. ACTIVE POWER from PULSES INPUT Unsigned 93F8 37880 (CH1) long AVER. REACT. POWER from PULSES INPUT Unsigned 93FA...
  • Page 85 SCU100 INSITE PRO M COMPACT USER MANUAL Addr. Addr. Word Slave Category Description Unit Format Access EQ Meter (hex) (dec) (16-bit) Modbus Resolution Res. Res. Reactive Power 942E 37934 2 Total Signed 0.01 0.01 Instantaneous Reactive Power 9430 37936 2 Signed 0.01 0.01...
  • Page 86 SCU100 INSITE PRO M COMPACT USER MANUAL Maximum values Addr. Addr. Word Slave Category Description Unit Format Access EQ Meter (hex) (dec) (16-bit) Modbus Resolution Res. Res. Maximum MAX LINE Unsigned 9461 37985 values CURRENT L1 long Maximum MAX LINE Unsigned 9463 37987...
  • Page 87 SCU100 INSITE PRO M COMPACT USER MANUAL Addr. Addr. Word Slave Category Description Unit Format Access EQ Meter (hex) (dec) (16-bit) Modbus Resolution Res. Res. Reset stored 949C 38044 1 Operations states Input 4 Unsigned Reset active energy import Resettable 949D 38045 1 Operations energy reg...
  • Page 88 SCU100 INSITE PRO M COMPACT USER MANUAL Addr. Addr. Word Slave Category Description Unit Format Access EQ Meter (hex) (dec) (16-bit) Modbus Resolution Res. Res. Reset counter (resettable active 94E1 38113 Other energy export) Unsigned Reset counter (resettable reactive energy 94E5 38117 Other...
  • Page 89 SCU100 INSITE PRO M COMPACT USER MANUAL Addr. Addr. Word Slave Category Description Unit Format Access EQ Meter (hex) (dec) (16-bit) Modbus Resolution Res. Res. Current transformer ratio secondary 9531 38193 Settings current Unsigned Voltage transformer ratio secondary 9533 38195 Settings current Unsigned...
  • Page 90 SCU100 INSITE PRO M COMPACT USER MANUAL Addr. Addr. Word Slave Category Description Unit Format Access EQ Meter (hex) (dec) (16-bit) Modbus Resolution Res. Res. I/O settings (incl pulse outputs) I/O signal mode 955A 38234 Settings port 4 Unsigned I/O settings (incl pulse outputs) I/O signal mode 955B...
  • Page 91 SCU100 INSITE PRO M COMPACT USER MANUAL Total active, reactive and apparent energy (import, export and net) Addr. Addr. Word Slave Category Description Unit Format Access EQ Meter (hex) (dec) (16-bit) Modbus Resolution Res. Res. Total 9570 38256 energies Active import Unsigned 0.01 0.01...
  • Page 92 IO module Alarm status Port 3 unsupported) Unsigned (yet E51A 58650 1 IO module Alarm status module unsupported) For the complete Modbus and SNMP map please refer to the one available for downloading on the ABB InSite pro M compact webpage...
  • Page 93 SCU100 INSITE PRO M COMPACT USER MANUAL Note...
  • Page 94 SCU100 INSITE PRO M COMPACT USER MANUAL Note...
  • Page 96 ABB S.p.A Electrification business Viale dell’Industria, 18 20010 Vittuone (MI) Italy new.abb.com/low-voltage...