The safety temperature limiter STW (6) is installed at the bottom of the reactor on the tank wall
and opens when a set limit of + 300 °C is exceeded.
In this case, the H3 indicator lights red and alarm F02 is displayed.
After falling below the limit value, the reset is carried out by means of automatic
RESET STW F02.
Temperature control takes place via the temperature control unit A3.
Both the safety temperature monitor TW and the safety temperature limiter STW are connected
to the temperature controller A3. This control unit realises the switching on and off of the
heating system according to the height of the temperatures on the container wall.
The outside temperature is displayed in the upper area of the container.