QUICK START GUIDE
Step 11 - Configure Controller per Galaxy Pulsar Edge Controller Quick
Start-Guide
The shelf is equipped with a 100A, 50mV battery shunt and Low Voltage Battery Disconnect (LVBD0.
1.
Verify and edit controller basic configuration parameters per site engineering instructions.
2.
Verify and edit Battery Shunt Settings to 100A, 50mV.
A. Controller display - follow path: Menu > Configuration > Shunt monitors > Plant Shunt A & Plant Shunt mV.
B. Web Pages or EasyView2 - select: Settings tab > Shunts > Plant Shunt
3. Set Rectifier Current Limit to 24A if two EP1600-UTEZ rectifiers are powered by a single C13 cord.
A. Controller display - follow path: Menu > Configuration > Rectifiers > Current Limit.
B. Web Pages or EasyView2 - select: Settings tab > Rectifiers > Thresholds > Current Limit
Information: Branch Protection Details
SHELF MODELS
J2007003 L005
J2007003 L005A
J2007003 L005C
Information: Rectifier Options
Rectifiers - Single phase,
hot-pluggable, fan-cooled
150027894EP0500-540W
CC109165602 EP1000-UTEZ:
1000W
CC109165610 EP1600-UTEZ:
1600W
1.
Output Current at 54.5v. Outputs are power limited, not current limited.
2.
Set rectifier current limit to avoid possible nuisance tripping
Page 4
© 2023 ABB. All rights reserved.
LOW RANGE
15A
2 x 15A
20A
Input
Vac
Aac
N/A
200 – 240 6.5
ONLY
N/A
100 – 120
12
ONLY
N/A &
200 – 240
6
CE
N/A
100 – 120
15
ONLY
N/A &
200 – 240 7.5
CE
BRANCH PROTECTION
North America
HIGH RANGE
15A
2 x 15A
15A
Max. Recommended Input AC
Current per Feed
1 – C14
2 – C14
1 – C20
15A
10A
20A
15A
15A
15A
10A
10A
10A
15A
15A
20A
10A
10A
10A
SPS -48V Shelf_QSG
CE
HIGH RANGE ONLY
15A
15A
15A
Output
Float Vdc
W
48 – 58
540
48 – 58
1000
1200
48 – 58
1600
A1