5.10 Heating Fan Low Noise

It is a function to reduce outdoor fan max rpm by adjusting low target pressure while heating mode.
■ Setting the function
Function
Heating Fan Low Noise
SE 11
■ Option Selection
Option
oFF
on
■ Detailed information
• This function is used with heat pump and heat recovery.
• The fan rpm is reduced by about 50 to 70% and may vary depending on environment and logic.
• Differences between SE9 and SE11
- SE9 (Noise Reduction): outdoor unit noise control + indoor unit noise control
- SE11 (Heating fan Low noise): outdoor unit fan noise control
(control factor : the outdoor temperature, heat exchanger temperature, indoor unit operation rate,
not always controlled)
ex) In case of SE11, optimize fan noise by adjusting the target low pressure when
the outdoor temperature is more than 5℃, the indoor unit operation rate is less
than 30%, and the heat exchanger temperature is more than 3℃
·Ask an authorized technician to setting a function.
·Change a power consumption or efficiency.
250
_TROUBLE SHOOTING GUIDE BOOK
Option
oFF, on
Detail of function
Off (Default)
Function enabled
5.11 Number of Partial Defrosts
This function is used for continuous heating control by option setting split defrost (heating cycle, upper /
lower valve control)
■ Setting the function
Function
Number of Partial Defrosts
SE 12
■ Option Selection
Option
Maximum Partial Defrost Cycles
oFF
None (Default)
op1
1
op2
2
op3
3
op4
4
op5
5
■ Detailed information
• This function is used with heat pump and heat recovery.
* Note : In order to prevent the accumulation of ice on the side of the outdoor unit, it is considered
that the number of partial defrost is minimized and that overall defrost is effective on the
outdoor unit side. however, on the indoor unit side, frequent overall defrost can cause the
lack of heating (according conversion to cooling cycle).
·Ask an authorized technician to setting a function.
·Change a power consumption or efficiency.
Option
oFF, op1~op11
Option
Maximum Partial Defrost Cycles
op6
6
op7
7
op8
8
op9
9
op10
10
op11
11