Toshiba Carrier BMS-SM1280HTLUL Service Manual page 40

Smart manager / central remote control
Hide thumbs Also See for Carrier BMS-SM1280HTLUL:
Table of Contents

Advertisement

13-5.Questions about Functions
No.
1
What is the procedure to create a setting file?
(*1)
2
How many air conditioners can be connected?
3
How many air conditioners can be connected?
4
How many central remote controllers can be
connected?
5
Can the BACnet system be used together?
6
Can the LONwork system be used together?
7
Can a remote monitoring system be used together?
8
Can a device in the AI-NETwork series be connected? Not possible. Use an air conditioning management system supported for the
9
Up to how many PCs can be connected?
(*1)
10
How many users can simultaneously access the
(*1)
system?
11
Can the system connect to an intra-company LAN?
(*1)
12
Is connection available via the Internet (WAN)?
13
Is connection available from a mobile phone?
14
If a failure occurs on the air conditioner, can mail be
sent?
15
Can a tenant name or other names be changed?
(*1)
16
Up to how many characters can be used for the name
(*1)
of tenant, etc.?
17
How many items does the alarm history save?
(*1)
18
How many days of power distribution data does the
(*1)
system save?
19
Can data be maintained in case of power outage?
20
Does turning off the controller require any specific
operation?
21
Does turning off the controller stop the air conditioner? The air conditioner where the remote controller or wireless adaptor is
22
Does a scheduled operation work only if a PC remains
(*1)
connected?
23
Does a PC need to remain connected to save power
(*1)
distribution data?
24
Is it possible to know an air conditioner failure without
(*1)
connecting a PC?
25
How many master schedules can be created?
(*1)
26
How many billing schedules can be created?
(*1)
27
What are the PC requirements for connecting to the
(*1)
controller?
Questions
Please read the Owner's manual of the Setting File Creation Software.
Up to 128 units of air conditioners can be connected. Note that up to 64 units
can be connected per TCC-LINK line.
Up to 64 units can be connected per TCC-LINK line. The controller has two
TCC-LINK lines, thus up to 128 units can be connected.
Up to 10 central remote control devices can be connected per TCC-LINK line.
The central control devices include a central remote controller.
Not possible. However, it is possible to use BACnet system together with a
central control device other than the Web-based central remote controller.
Possible. Check that it works.
Not possible. However, it is possible to use a remote monitoring system
together with a central control device other than the Web-based central
remote controller.
AI-NETwork series.
Up to 4 users can simultaneously log on.
Up to 4 PCs can be simultaneously connected.
Without simultaneous connection, the number of PCs connected has no
limitation.
Possible. However, check with your network administrator if the connection
is available.
Not available.
Not possible.
You can use the Setting File Creation Software to change the name of a floor,
a tenant, an area, and an air conditioner.
For a floor name: 20 bytes,
for a tenant name: 30 bytes,
for an area name: 20 bytes, and
for an air conditioner name: 20 bytes.
It saves up to 1,024 items. If the alarm history items exceed 1,024, the item
is deleted sequentially from the oldest one.
The system saves the 45 days of daily report files and the 3 months of
monthly report files.
Data will be backed up before being saved. If power outage occurs during the
data saving, the backup data is restored, thus the data is protected.
No specific operation is necessary.
connected does not stop when the controller is turned off.
An air conditioner other than the above stops.
No. Because the power distribution data are saved inside the controller, the
PC does not need to remain connected.
An alarm can be set to go off with a buzzer or other means connected to the
alarm external output of no-voltage A contact.
An alarm can be set to go off with a buzzer or other means connected to the
alarm external output of no-voltage A contact.
Up to 32 schedules can be created for each master schedule and billing
schedule.
1.PC running Window XP or Vista without any problem. Also, the PC
must have Internet Explorer Version 6.0, 7.0 or 8.0 or Firefox 2.0, 3.0,
3.5 or 3.6.
2.If you use the Monthly Report Creation Software, you need to install
Microsoft Excel 2002 or later on your computer.
40
Answer