Toshiba BMS-SM1280ETLE Service Manual page 23

Smart manager with data analyzer
Table of Contents

Advertisement

<DS25>
<1> Always OFF
• Always set this bit to OFF.
<2> Synchronization of zone setting data
OFF: With synchronization
ON: Without synchronization
This bit specifies whether to perform synchronous communication of zone setting
data between Smart Manager with data analyzers.
* When this bit is set to ON (without synchronization), synchronous communication
is not performed, and when zone setting is made, the data is not reflected in other
Smart Manager with data analyzers.
<3> Always OFF
• Always set this bit to OFF.
<4> Fire alarm input switching (Set this switch to match the fire alarm input connection set in chapter 4.)
Set OPEN or CLOSE input junction pegged to fire alarm.
• OFF: Set CLOSE input junction pegged to fire alarm.
COM-DI
DI3
(Normal)
• ON: Set OPEN input junction pegged to fire alarm.
COM-DI
DI3
(Normal)
Termination
The termination switches for TCC-LINK are placed in the central controller box. Detach the panel when configuring
termination setting.
NOTE
TCC-LINK connection is terminated on indoor units. Set SW 200 to "Open" for both TCC-LINK 1 and 2.
SW200
ON
23
COM-DI
DI3
(Fire alarm)
COM-DI
DI3
(Fire alarm)
SW200
TCC-LINK termination switches
ON
1
2
TCC-LINK1
Open
TCC-LINK2
Open
ON
1
2
TCC-LINK1
Open
TCC-LINK2
100Ω
Factory default: All OFF
DS25
ON
1
2 3 4
OFF
ON
1
2
TCC-LINK1
100Ω
TCC-LINK2
Open
ON
1
2
TCC-LINK1
100Ω
TCC-LINK2
100Ω