Line distance protection REL670
Version 2.2
Directional over/underpower protection GOPPDOP/
GUPPDUP
The directional over-/under-power protection (GOPPDOP/
GUPPDUP) can be used wherever a high/low active,
reactive or apparent power protection or alarming is
required. The functions can alternatively be used to check
the direction of active or reactive power flow in the power
system. There are a number of applications where such
functionality is needed. Some of them are:
• detection of reversed active power flow
• detection of high reactive power flow
Each function has two steps with definite time delay.
Broken conductor check BRCPTOC
The main purpose of the function Broken conductor check
(BRCPTOC) is the detection of broken conductors on
protected power lines and cables (series faults). Detection
can be used to give alarm only or trip the line breaker.
Voltage-restrained time overcurrent protection
VRPVOC
Voltage-restrained time overcurrent protection (VRPVOC)
function can be used as generator backup protection
against short-circuits.
The overcurrent protection feature has a settable current
level that can be used either with definite time or inverse
time characteristic. Additionally, it can be voltage controlled/
restrained.
One undervoltage step with definite time characteristic is
also available within the function in order to provide
functionality for overcurrent protection with undervoltage
seal-in.
Average Power Transient Earth Fault Protection
APPTEF
The APPTEF (Average Power Transient Earth Fault
Protection) function is a transient measuring directional
earth-fault protection. Determination of the earth fault
direction is based on the short-term built-up transient at the
beginning of the earth fault. This transient is to a large
extent independent of the neutral point treatment. This
means that the function can be used without any
modification in all types of high-impedance grounded,
resonant grounded or isolated power systems.
For a resonant grounded system, the correct directional
measurement is ensured regardless of how many Petersen
coils are used throughout the interconnected power
network. The function is not sensitive to the actual
compensation degree of the coils. It will operate equally well
in an under- or over-compensated system. Parallel neutral
resistor to the Petersen coil are not needed to correctly
determine earth fault direction. However, these neutral
resistors can still be used if already installed in the network.
Hitachi Energy
SEMOD175421-4 v7
SEMOD171446-5 v2
GUID-935E1CE8-601F-40E2-8D22-2FF68420FADF v6
GUID-A16ED4BC-855F-4561-8512-B4F30775784F v1
© 2017 - 2022 Hitachi Energy. All rights reserved
The function is suitable to be used in distribution and in
meshed HV sub-transmission networks using high-
impedance grounding. In meshed systems a directional
permissive scheme is required in order to ensure selective
tripping of a faulty line. Alternatively, the function can be
used solely for signaling of the earth-fault location to the
SCADA system when the power network is allowed to
operate for a longer time with an earth-fault being present.
8. Voltage protection
Two-step undervoltage protection UV2PTUV
Undervoltages can occur in the power system during faults
or abnormal conditions. The two-step undervoltage
protection function (UV2PTUV) can be used to open circuit
breakers to prepare for system restoration at power outages
or as a long-time delayed back-up to the primary protection.
UV2PTUV has two voltage steps, each with inverse or
definite time delay.
It has a high reset ratio to allow settings close to the system
service voltage.
Two step overvoltage protection OV2PTOV
Overvoltages may occur in the power system during
abnormal conditions such as sudden power loss, tap
changer regulating failures, and open line ends on long
lines.
Two step overvoltage protection (OV2PTOV) function can
be used to detect open line ends, normally then combined
with a directional reactive over-power function to supervise
the system voltage. When triggered, the function will cause
an alarm, switch in reactors, or switch out capacitor banks.
OV2PTOV has two voltage steps, each of them with inverse
or definite time delayed.
OV2PTOV has a high reset ratio to allow settings close to
system service voltage.
Residual overvoltage protection, two steps
ROV2PTOV
Residual voltages may occur in the power system during
earth faults.
Two step residual overvoltage protection (ROV2PTOV)
function calculates the residual voltage from the three-
phase voltage input transformers or measures it from a
single voltage input transformer fed from an open delta or
neutral point voltage transformer.
ROV2PTOV has two voltage steps, each with inverse or
definite time delay.
A reset delay ensures operation for intermittent earth faults.
1MRK 506 372-BEN Q
M13789-3 v14
M13798-3 v17
M13808-3 v12