Advertisement

Line distance protection REL670
Version 2.2
Current protection
Table 54. Instantaneous phase overcurrent protection PHPIOC
Function
Operate current
Reset ratio
Operate time at 0 to 2 x I
set
Reset time at 2 x I
to 0
set
Critical impulse time
Operate time at 0 to 10 x I
set
Reset time at 10 x I
to 0
set
Critical impulse time
Dynamic overreach
90
M12336-1 v14
Range or value
(5-2500)% of lBase
> 95% at (50–2500)% of IBase
Min. = 15 ms
Max. = 25 ms
Min. = 15 ms
Max. = 30 ms
10 ms typically at 0 to 2 x I
set
Min. = 5 ms
Max. = 15 ms
Min. = 25 ms
Max. = 40 ms
2 ms typically at 0 to 10 x I
set
< 5% at t = 100 ms
© 2017 - 2022 Hitachi Energy. All rights reserved
Accuracy
±1.0% of I
at I ≤ I
r
r
±1.0% of I at I > I
r
-
-
-
-
-
-
-
-
1MRK 506 372-BEN Q