Download Print this page

Installation Of Optional Air Panel: P-Ap160Na1 / P-Ap160Nae - Hitachi P-AP160NA1 Installation And Operation Manual

Indoor units system free
Hide thumbs Also See for P-AP160NA1:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 7

installation of optional air panel: p-ap160na1 / p-ap160nae

7.2 HIGH sPEED sETTING fuNCTION
This function allow to set the air flow volume higher than normal
air flow volume steps. It is for high height ceiling on site. Set the
fan speed from control remote function selection menu depen-
ding on a ceiling height as shown in the table below.
7.3 CIrCuLATION fuNCTION AT HEATING THErmO-Off
This function maintains the fan operation by the set air flow volume at the heating Thermo-OFF. It is for improvement of temperature
distribution at high height ceiling site.
7.4 mOTION sENsOr fuNCTION
Only for panel with motion sensor model P-AP160NAE with PC-
ARf remote control installation.
The motion sensor detects a human activity by the change of
the infrared light. This function saves the air conditioning capacity
(adjusting the set temperature, the air flow volume and the air
flow direction) automatically depending on a situation. The opera-
tion after the motion sensor detects as absence can be selected
from "Running", "Stand-by" or "Stop" on the remote control switch
with the capacity saving.
in the case that the indoor units are operated by 2 remote con-
trol switches, the motion sensor setting is available only from the
main remote control switch.
7.5 sETTING THE fILTEr INDICATION INTErvAL
The fiLTER interval indication on the remote control switch can be set in several interval. Refered to remote control installation and
Operation manual.
7.6 INDIvIDuAL LOuvEr sETTING
The individual control setting for each louver is available with PC-ARf remote control. Refered to remote control installation and Ope-
ration manual.
8 INSTALLATION OF OPTIONAL AIR PANEL: P-AP160NA1 / P-AP160NAE
8.1 fACTOry-suPPLIED ACCEssOrIEs
C A u T I O N
When the air panel is unpacked, place it on insulation material, etc. to protect the sealing insulation from scratches
Check to ensure that the accessories are packed with the air panel.
Accessory
Long Screw
(m6 Cross
Screw)
Relay Wire
A: 3 poles /
A
B: 5 poles
if any of these accessories are not packed in the packing, please contact your contractor.
14
P-AP-
P-AP-
160NA1
160NAE
For fixing air
4
4
for motion
-
1
B
PmmL0223A rev.0 - 05/2012 - P5415035
Ceiling Height
1.0 to 3.0HP
Below 2.7m
2.7 to 3.0m
3.0 to 3.5m
N O T E
The indoor unit without the motion sensor and the indoor unit with
the motion sensor can be mixed to install. In this case, when the
operation is stopped by the motion sensor control, the indoor unit
without the motion sensor will also stop the operation.
The motion sensor control adjusts automatically the following
items depending on a situation.
Setting Temperature: The temperature is adjusted 1ºC or 2ºC
for saving capacity.
Air Flow Volume: The air flow volume is adjusted to lower one
volume or to "Slo" (except during the dry operation).
* Air Flow Direction: The air flow direction is adjusted to hori-
zontal.
Purpose
Accessory
Wiring
panel
Cover
Plastic
sensor
Band
Setting of Remote Control
Switch
4.0 to 6.0HP
Below 3.2m
Standard
3.2 to 3.6m
High Speed (1)
3.6 to 4.2m
High Speed (2)
P-AP-
P-AP-
160NA1
160NAE
-
-
Purpose
for protection
1
of relay
connector
for clamping
wiring cover
3
and relay
connector

Advertisement

Chapters

loading

This manual is also suitable for:

P-ap160naeRci-(1.0-6.0)fsn3