Terminals for connection of external batteries are on the rear of the receiver (
Figure 1: Location of D6100IPv6 Battery Terminals and D6600 Battery
Connector
Receivers are not shown to scale.
3.3
Fire Alarm Applications
The D6600/D6100IPv6 can be used for Central Station Protective Signaling when it is installed and
used in compliance with NFPA 72 and ANSI/NFPA 70. Installation limits for digital alarm
communicator receivers (DACR) are under the local AHJ.
3.4
Rack Mount Instructions
Maintain a 6.5 mm (0.25 in.) gap, or greater, between power limited and non-power limited
circuit wiring.
The D6600 and D6100IPv6 must be installed in a rack.
The D6100IPv6 installation must consist of the following:
D6100IPv6 Communication Gateway Receiver
D6100RMK Rack Mount Kit
GlobTek, Inc. Model DA-42-18L Transformer
Plug the D6600 AC cord or the D6100IPv6 AC transformer into an outlet inside the rack only if the
outlet is wired according to Article 760 of the NEC. Rack mounting is required (according to NFPA
72-2002 4.4.1.4.2.1) to meet the mechanical protection requirement when using the type of AC cord
provided with the D6600. A UL Listed rack is required for fire protective service.
4.0
Standby Power
4.1
Connecting External Batteries
Use only approved standby batteries. Battery wiring must run from the receiver through the UL
Listed rack, exit from the rack through a conduit connection, and terminate at a UL Listed battery
enclosure suitable for the size and number of batteries used.
4.2
Uninterruptible Power Supply (UPS) Requirements
A UL1481 Listed UPS for Commercial Fire Use is required when using the D6600.
When using a UPS with the D6100IPv6, a UL1481 Listed UPS for Commercial Fire Use is required.
5.0
Input and Output Ports
5.1
UPS Monitoring through CPU Programmable Input Ports
Wiring must run from the receiver through the UL Listed rack, exit from the rack through a conduit
connection, and terminate at the external UPS for UL applications.
© Bosch Security Systems, Inc., 2012
UL864 & UL1610 Installation Supplement
Page 3
on page 3).