TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. G
... Use in potentially explosive atmospheres
Preconditions for safe operation of the positioner
When using in hazardous areas, observe the following points:
Observe the specification and special conditions
applicable for the device in accordance with the
relevant valid certificate.
Manipulation of the device in any form by the user is
not permitted. Only the manufacturer or an explosion
protection specialist may modify the device
The IP 65 / NEMA 4x IP rating is only achieved if the
splash guard is screwed in place. Operating the unit
without splash guard cap is prohibited.
The device may only be operated using instrument air
that is free from oil, water and dust. The use of
flammable gas, oxygen, or oxygen-enriched gas is not
permitted.
High / recurring charging processes in gas zones must
be excluded by the operator.
Cable gland
Limited temperature range of the M20 × 1.5 plastic cable
gland for explosion protection variants:
The permissible ambient temperature range is
−20 to 80 °C (−4 to 176 °F).
When using the cable gland, you need to make sure
that the ambient temperature is within the
permissible range plus 10 K or that they are suited in
terms of the minimal ambient temperature.
The cable gland must be installed in the housing with
a tightening torque of 3.8 Nm. When installing the
connection of the cable gland and cable, check for
tightness to ensure that the required IP rating is met.