40
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. G
—
... Use in potentially explosive atmospheres
EAC TR-CU-012
Ex marking
Ex marking
Marking
1Ex ia IIC T6/Т4 Gb Х
1Ex ib IIC T6/Т4 Gb Х
Certificate
EAC TR-CU-012
Type
Intrinsically safe equipment
Standards
EN 60079-0, EN 60079-11
Special conditions
•
The power supply for the 'Feedback on the actuator
position using proximity switches (Pepperl & Fuchs SJ2-
SN)' circuit must be provided intrinsically safe in
accordance with the PTB 00 ATEX 2049 X / RU C-
DE.AA87.B.00394 certificate according to application
type 2.
•
It is only permissible to connect, disconnect, and switch
live circuits during installation or maintenance, or for the
purpose of carrying out repairs.
Note
It is considered very unlikely that a potentially hazardous
atmosphere would be present in Zone 2 at the same time
that installation or maintenance or repair work was being
carried out.
•
Only non-flammable gases must be used for pneumatic
power supply.
•
Only use suited cable entries that meet the requirements
of EN 60079-11.
Temperature characteristic curves
Intrinsically safe circuit according to ATEX and EAC /
TR CU 012/2011
•
Equipment Category 1: Use in Zone 0
•
Equipment Category 2: Use in Zone 1
•
Equipment Category 3: Use in Zone 2
Temperature Data
Temperature class
Ambient temperature Ta
T4
−40 to +85 °C
T6*
−40 to 40 °C*
*
When using the 'Plug-in module for digital feedback' in temperature
class T6, the maximum permissible ambient temperature range is -
40 to +35 °C.
Electrical Data
In type of protection 'Intrinsic safety Ex ia, Ex ib', only for
connection to a certified intrinsically safe circuit.
Current circuit (terminal) Electrical information (maximum values)
Signal circuit
U
= 30 V
i
(+11 / -12)
I
= 320 mA
i
P
= 1.1 W
i
Contact input
U
= 30 V
i
(+81 / -82)
I
= 320 mA
i
P
= 1.1 W
i
Switch output
U
= 30 V
i
(+83 / -84)
I
= 320 mA
i
P
= 500 mW
i
Feedback on the
For maximum values, see EU-Type examination
actuator position using
certificate PTB 00 ATEX 2049 X /
proximity switches,
RU C-DE.AA87.B.00394 Pepperl & Fuchs Type 2
(Pepperl & Fuchs SJ2-SN)
proximity switches
(Limit1: +51 / −52),
(Limit2: +41 / -42)
Plug-in module for
U
= 30 V
i
digital feedback
I
= 320 mA
i
(+51 / -52)
P
= 250 mW
i
(+41 / -42)
Plug-in module for
U
= 30 V
i
analog feedback
I
= 320 mA
i
(+31 / -32)
P
= 1.1 W
i
Interface with the TZIDC
U
= 5.4 V
0
Remote Sensor
I
= 74 mA
0
(X2-2: +Uref, X3-2: GND,
P
= 100 mW
0
X3-1: Signal)
C
= negligibly small
i
L
= negligibly small
i
Local communication
Only for connection to a programming device
interface (LCI)
using an ABB LCI adapter (Um ≤ 30 V DC)
outside the hazardous area.
C
= 6.6 nF
i
L
= negligibly small
i
C
= 14.5 nF
i
L
= negligibly small
i
C
= 14.5 nF
i
L
= negligibly small
i
C
= 3.7 nF
i
L
= negligibly small
i
C
= 6.6 nF
i
L
= negligibly small
i
Ex ia or Ex ib type of
protection
IIC:
L
= 5 mH
0
C
= 2 μF
0
IIB:
L
= 5 mH
0
C
= 10 μF
0