Short-circuit detection
The diagnostics for short circuit to ground can be configured for the voltage output type. A
short-circuit detection is not possible for small output values; the output voltages must
therefore be below -0.1 V or above +0.1 V.
Open-circuit detection
The diagnostics for open circuit can be configured for the current output type. An open-circuit
detection is not possible for small output values; the output voltages must therefore be below
-0.2 mA or above +0.2 mA.
4.3

Declaration of parameters

Missing supply voltage L+
Enabling of the diagnostics, with missing or too little supply voltage L+.
Wire break
Enabling of the diagnostics if the line to the actuator is broken.
Short-circuit to ground
Enabling of the diagnostics if a short-circuit of the output to M
Overflow
Enabling of the diagnostics when the output value exceeds the overrange.
Underflow
Enabling of the diagnostics when the output value violates the underrange.
Reaction to CPU STOP
Determines the reaction of the output to the CPU going into STOP state.
Substitute value
The substitute value is the value that the module outputs in case of a CPU STOP.
Analog output module AQ 4xU/I ST (6ES7532-5HD00-0AB0)
Manual, 07/2014, A5E03484696-AC
Parameters/address space
4.3 Declaration of parameters
occurs.
ANA
17