9.11 Parameters

9.11
Parameters
"Parameter assignment" means setting the module properties. This includes setting
addresses, enabling alarms and defining communication properties.
You assign the property parameters for the CPUs in the area navigation, in the STEP 7
Inspector window. The CPUs have general parameters and R/H-specific parameters. Some
parameters must be identical for both CPUs. STEP 7 applies these parameters to the second
CPU. Other parameters must be different on each CPU (for example device IP addresses). If
your configuration is not consistent, STEP 7 will point out the conflict.
Reference
You can find a detailed description of all CPU parameters in the STEP 7 online help.
9.12

Process images and process image partitions

9.12.1

Process image - overview

Process image inputs and outputs
The process image of the inputs and outputs is an image of the signal states. The CPU
transfers the values from the input and output modules to the process image inputs and
outputs. At the start of the cyclic program, the CPU transfers the process image output as a
signal state to the output modules. The CPU then transfers the signal states of the input
modules to the process image inputs.
Advantages of the process image
A consistent map of the process signals is available via the process image during cyclic
program execution. If a signal state at an input module changes during program execution,
the signal state is retained in the process image. The CPU does not update the process image
until the next cycle.
Consistency of the process image
When the process image is updated, the S7-1500R/H redundant system accesses the data of
each submodule as consistent data. This behavior is identical to that of S7-1500 CPUs.
The maximum data width that is accessed as consistent data for each submodule depends on
the IO system. For PROFINET IO, for example, this data width is 1024 bytes.
314
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF