Load current supply modules
The load current supply modules have automatic input voltage range switching. The table
below shows the available load current supply modules.
Short designation
Article number
Equipment Manual
Rated input voltage
Output voltage
Rated output current
Power consumption
Using a SITOP power supply as an alternative to a load power supply
Alternatively, an external 24 V power supply from the SITOP range
(https://mall.industry.siemens.com/mall/en/WW/Catalog/Products/10008864) (SITOP smart or
SITOP modular) can be used:
• With redundant installation
(https://support.industry.siemens.com/cs/ww/en/view/109768676) of the 24 V power
supply as protection against failure of a power supply unit
• With buffering of the 24 V power supply (e.g. with DC UPS) as protection against power
failure
• With selective monitoring of 24 V loads as protection against overload or short-circuit
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF
PM 70 W 120/230 V AC
6EP1332-4BA00
120/230 V AC,
with automatic switchover
24 V DC
3 A
84 W
System overview
5.5 Power supply
PM 190 W 120/230 V AC
6EP1333-4BA00
120/230 V AC,
with automatic switchover
24 V DC
8 A
213 W