Siemens SIMATIC S7-1500 System Manual page 132

Redundant system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Property
System power supply (PS)
Load current supply PM
As of FW version V3.0 of the R-CPUs, the firmware between CPU and display is no longer separated. The firmware of the
1)
display is included in the firmware of the R-CPU.
If you use PROFINET devices that do not support H-Sync forwarding in S7-1500R, additional cycle time increases may
2)
occur in the RUN-Redundant system state. If the cyclic program exceeds the cycle monitoring time, the time error OB
(OB 80) may be started. You can find more information in the Events and OBs section.
Special case: Operating R/H CPU individually
You can operate an R/H CPU as a single CPU. If you do, please note the following:
• You always configure 2 R-CPUs or H-CPUs for S7-1500R/H, even if you only set up one CPU.
• The MAINT LED on the CPU is always yellow (maintenance demanded):
– The R/H system is not in redundant mode.
– No partner CPU was found.
Software requirements
Table 6- 2
Requirement
CPU 1513R-1 PN, CPU 1515R-2 PN, CPU 1517H-3 PN
CPU 1518HF-4 PN
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF
Requirement
System power supply PS for the R/H CPUs
The use of the PS is optional.
Suitable system power supplies:
PS 25W 24V DC
PS 60W 24/48/60V DC
PS 60 W 120/230V AC/DC
Load current supply PM for the R/H CPUs
The use of the PM is optional.
Suitable load current supplies:
PM 70 W 120/230 V AC
PM 190 W 120/230 V AC
Software requirements
Application planning
6.1 Requirements
Required STEP 7 version
SIMATIC STEP 7 Professional,
V15.1 or later
SIMATIC STEP 7 Professional V17
or higher
131

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500r/h

Table of Contents