System overview
5.2 Configuration
5.2.2

Structure of the S7-1500H redundant system

Configuration
The S7-1500H redundant system comprises the following components:
• 2 H-CPUs
• 2 SIMATIC Memory Cards
• 4 synchronization modules (two synchronization modules in each H-CPU)
• 2 redundancy connections (two duplex fiber-optic cables)
• If applicable, IO devices
• optional load current supply
• optional system power supply (only via active backplane bus)
• optional communications processors CP 1543-1 (only via active backplane bus)
The S7-1500H redundant system should be mounted either on one shared rail or on two
separate rails. You connect the two CPUs with fiber-optic cables to two synchronization
modules in each CPU. You set up the PROFINET network via the PROFINET interfaces X1 P1R
and X1 P2R of the CPUs.
Configuration example
Optional load current supply
CPU (with two synchronization modules, connected underneath, not visible in the diagram)
Rail with integrated DIN-rail profile
Redundancy connections (fiber-optic cables)
PROFINET cable
Figure 5-15
S7-1500H configuration example
86
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF