Failure Of Profinet Lines In Two Places In A Line Topology With S2 Devices - Siemens SIMATIC S7-1500 System Manual

Redundant system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Application planning
6.5 Failure scenarios
4. The S1 devices in PROFINET ring 1 are no longer accessible by the new primary CPU. The S1
devices return to the substitute values.
5. The failure of the primary CPU affects the process, since the S1 devices in the PROFINET ring
1 can no longer be accessed from the primary CPU.
Diagnostics
System state, operating states and error displays after primary-backup switchover:
• Redundant system → RUN-Solo system state
• Primary CPU (previously backup CPU) → RUN operating state
– MAINT LED → yellow light: The H-system is not in the RUN-Redundant system state. No
– ERROR LED → flashes red: One or more IO devices have failed.
• Backup CPU (previously primary CPU) → failed
Note
To get detailed diagnostics information, evaluate the diagnostics buffer.
Solution
Replace the defective CPU. You can find additional information on the procedure in the
section Replacing defective R/H CPUs (Page 446).
6.5.4.7

Failure of PROFINET lines in two places in a line topology with S2 devices

Introduction
The following failure scenario describes the effects of a defect in the PROFINET lines at two
points in a line topology with S2 devices.
222
partner CPU has been found in the redundant system.
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF