12.4 Operating and system states
⑥SYNCUP → RUN-Redundant, RUN-Syncup → RUN-Redundant
Transition
Description
System state
SYNCUP → RUN-Redundant
transition
The redundant system switches from SYNCUP to the RUN-Redundant system
state if SYNCUP has successfully run.
In the RUN-Redundant system state, the two CPUs execute the user program
synchronously.
Note: A temporary increase in the cycle time can occur upon a system
state transition SYNCUP → RUN-Redundant. Configure a sufficiently long
maximum cycle time for the CPUs.
Operating state
RUN-Syncup → RUN-Redundant
transitions
The primary CPU switches from the RUN-Syncup operating state to the RUN-
Redundant operating state if SYNCUP has successfully run.
SYNCUP → RUN-Redundant
The backup CPU switches from the SYNCUP operating state to the RUN-
Redundant operating state if SYNCUP has successfully run.
Central modules on the rail of the backup CPU server are only put into opera-
tion after reaching RUN-Redundant. If loaded, the corresponding OBs (e.g.
OB 83) are called.
⑦RUN-Redundant → RUN-Solo, RUN-Redundant → RUN
Transition
Description
RUN-Redundant → RUN-Solo
System state
transition
The redundant system switches from the RUN-Redundant system state to the
RUN-Solo system state (loss of redundancy) if:
You POWER OFF one of the CPUs.
or
A CPU detects an error which prevents further work.
or
The cycle time was exceeded once, see section Events and OBs (Page 323)
or
You set one of the CPUs to STOP with the PG/PC, the display, the RH_CTRL
instruction (Mode 8/9) or the mode selector.
The primary CPU switches to RUN or the backup CPU becomes the primary
CPU and switches to RUN.
Operating state
RUN-Redundant → RUN
transition
The primary CPU switches from the RUN-Redundant operating state to the
RUN operating state and continues to execute the user program.
408
Effects
This system state tran-
sition does not have
any effect on data.
Communication con-
nections (HMI, PG/PC)
on the backup CPU
become available.
Both CPUs process the
user program synchro-
nously.
Effects
This system state tran-
sition does not have
any effect on the data.
This operating state
transition does not
have any effect on
data.
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF