4-2-3. Unit-related item sheet (BACnet
Unit-related item sheet (entire view)
Unit-related item sheet (enlarged view)
®
[1] BACnet
function: Entering the apportioned electric energy value
Enter the apportioned electric energy values in the AE-200 BACnet
same timing as that in 4-2-2 [2].
① Enter the first checked date and time.
®
② Use BACnet
Electric Energy" (AC_01xx39: xx = Group number (01–50)) or "Interlocked Units Apportioned Electric
Energy" (AC_61aa39: aa = Interlocked unit address (01–50)) objects and enter the electric energy values
before the trial run.
"Present_Value" property value × 0.1 = Electric energy [kWh]
Note
For how to operate BACnet
Trial Run Tool–.
Enter the electric energy value for the representative single air conditioning unit if the group consists of
multiple units. Enter "-" for the air conditioning units other than the representative unit.
[2] Checking the generation of trend log object
Check that the BACnet
AE-200/AE-50/EW-50 Instruction Book –BACnet
®
③ ‌ Use BACnet
(LOG_01xx83) or "Trend Log Interlocked Units Apportioned Electric Energy" (LOG_61aa83: aa =
Interlocked unit address (01–50)) objects exist, and when they exist, insert a check mark.
WT08246X03
[1]
Trial Run Tool and read the "Present_Value" property values of the "Group Apportioned
®
Trial Run Tool, refer to the AE-200/AE-50/EW-50 Instruction Book –BACnet
®
trend log object has been generated. If the trend log object is disabled, refer to the
Trial Run Tool and check whether the "Trend Log Group Apportioned Electric Energy"
®
)
[2]
®
function in the unit-related item sheet at the
®
Setting Tool– and enable the trend log object.
14
[1]
[2]
®