The following shows an operation example of the apportioned electricity billing function of the AE-200 (when it is
started at 10:00).
The example assumes that there are no apportioned results in the past (at the default settings) and that 180000
(1800 seconds = 30 minutes) is set in the "Log_interval" property.
The time when the apportioned result is stored for the first time is indicated by bold characters.
Accumulator and trend log object update timing
Apportioned calculation
Time
(cumulative value)
<> indicates the cumulation
range.
(Unit [0.1 kWh])
10:00
10:15
Apportioned result [1]
10:30
(Example: 20)
<10:00–10:30>
10:45
Apportioned result [2]
11:00
(Example: 50)
<10:00–11:00>
11:15
Apportioned result [3]
11:30
(Example: 90)
<10:00–11:30>
11:45
12:00
Apportioned result [4]
<10:00–12:00>
WT08246X03
"Present_Value" of the
accumulator object
(Unit [0.1 kWh])
0
Update (+ 0) = 0
(0 because of the
shortage of calculation target)
Update (+ 0) = 0
(0 because of the
shortage of calculation target)
Update (+ Apportioned result
[2] - [1])
= 0 + (50 - 20) = 30
Update (+ Apportioned result
[3] - [2])
= 30 + (90 - 50) = 70
8
"Log_Buffer" of the trend
log object
Store (0)
Store (0)
Store (Apportioned result
[2] - [1])
(30)
Store (Apportioned result
[3] - [1])
(70)