The equipment is installed outdoors. The site selection requirements are as
follows:
Issue Draft A
(2022-09-07)
The equipment is heavy. Ensure that the installation surface is solid enough to
bear the weight of the equipment.
The site is not located in a low-lying land. The horizontal level of the site is
above the highest water level of that area in history.
The ground is solid without spongy or soft soil, and is not prone to water
accumulation or subsidence.
The site is located in a well-ventilated area.
The site is far away from sources of strong variation, loud noises, and strong
electromagnetic interference.
The site is not above any underground facilities.
The site must be a class C or higher environment but not a class D or E
environment.
The site is far away from dust, cooking fume, harmful gases, and corrosive,
flammable, or explosive objects.
The site is in an open area and at least 10 m away from any obstacles in all
directions.
The site is at least 50 m away from residential areas.
The site temperature is within the range of –25°C to +60°C. If the temperature
exceeds 55°C, the equipment must be installed in a shaded area.
If the equipment is installed in a place with dense vegetation, in addition to
routine weeding, harden the ground under the equipment to prevent weeds
from growing.
NO TE
● Class C environment: Outdoor areas more than 500 m away from the sea. If a site
is near a pollution source, it must be 1500–3000 m away from heavy pollution
sources, such as smelteries, coal mines, and thermal power plants; 1000–2000 m
away from medium pollution sources such as chemicals, rubber, and galvanization;
or 500–1000 m away from light pollution sources, such as packing houses,
tanneries, boiler rooms, slaughterhouses, landfill sites, and sewage treatment
plants.
● Class D environment: Sea environments or outdoor areas within 500 m away from
the sea. If a site is near a pollution source, it is within 1500 m away from heavy
pollution sources such as smelteries, coal mines, and thermal power plants, within
1000 m away from medium pollution sources such as chemical, rubber, and
galvanization industries, or within 500 m away from light pollution sources such as
packing houses, tanneries, boiler rooms, slaughterhouses, landfill sites, and sewage
treatment plants.
● Class E environment: Special environments, such as underground or underwater
environments.