Application layer
The application layer is responsible for performing operations on data objects defined by the device or on
the device itself. These operations include returning actual values (read function), assigning new values
(write function) if the object represents control points, arming and energizing the output point (select,
operate or direct operate functions) and if counters are used, reading actual values and clearing the
counters. DNP3 uses the term point to identify an entity, and these entities can be categorized into point-
types, such as analogs or binaries. Points are addressed by giving them an index number and an object
is a formatted representation of data from a point. These objects can be assigned to classes in order to
organize events and current values into categories. The DNP3 protocol defines four data classes to
organize data reporting.
Communication modes
The IED supports four DNP3 communication modes.
Quiescent operation
Unsolicited report-by-exception operation
Polled report-by-exception operation
Polled static operation
2.2

Documentation

This implementation of DNP3 is fully compliant with DNP3 Subset Definition Level 2, and contains
significant functionality beyond Subset Level 2. See the device profile for further information.
DNP, 670 series
Communication protocol manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 2
DNP3 overview
GUID-7966A3BB-DC5A-47CF-B78D-D8BF1373C308 v1