Hitachi Relion 670 Series Communication Protocol Manual page 46

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 4
DNP3 parameters
Name
Values (Range)
tVREvBufTout2
0.00 - 60.00
UREvCntThold3
1 - 100
tVREvBufTout3
0.00 - 60.00
DelOldBufFull
No
Yes
ExtTimeFormat
LocalTime
UTC
DNPToSetTime
No
Yes
tSynchTimeout
30 - 3600
TSyncReqAfTout
No
Yes
Averag3TimeReq
No
Yes
PairedPoint
No
Yes
tSelectTimeout
1.0 - 60.0
tBrokenConTout
0 - 3600
tKeepAliveT
0 - 3600
Table 27:
MST4TCP Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
SlaveAddress
0 - 65519
MasterAddres
0 - 65519
ValMasterAddr
No
Yes
MasterIP-Addr
0 - 18
MasterIPNetMsk
0 - 18
Obj1DefVar
1:BISingleBit
2:BIWithStatus
Obj2DefVar
1:BIChWithoutTime
2:BIChWithTime
3:BIChWithRelTim
e
Obj3DefVar
1:DIWithoutFlag
2:DIWithFlag
Table continues on next page
40
Unit
Step
Default
s
0.01
5.00
-
1
5
s
0.01
5.00
-
-
No
-
-
UTC
-
-
No
s
1
1800
-
-
No
-
-
No
-
-
Yes
s
0.1
30.0
s
1
0
s
1
10
Unit
Step
Default
-
-
Disabled
-
1
1
-
1
1
-
-
Yes
IP
1
0.0.0.0
Address
IP
1
255.255.255.255
Address
-
-
1:BISingleBit
-
-
3:BIChWithRelTim
e
-
-
1:DIWithoutFlag
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK511391-UUS Rev. L
Description
Unsolicited response class 2 event buffer
timeout
Unsolicited response class 3 event count
report treshold
Unsolicited response class 3 event buffer
timeout
Delete oldest event when buffer is full
External time format
Allow DNP to set time in IED
Time synch timeout before error status is
generated
Time synchronization request after timeout
Use average of 3 time requests
Enable paired point
Select timeout
Broken connection timeout
Keep-Alive timer
Description
Operation Disabled/Enabled
Slave address
Master address
Validate source (master) address
Master IP-address
Master IP net mask
Object 1, default variation
Object 2, default variation
Object 3, default variation
Communication protocol manual
PID-4137-SETTINGS v6