Hazardous Voltage.
Hazardous Voltage.
Will cause death or serious injury.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before
Turn off and lock out all power supplying this device before
working on this device.
working on this device.
Replace all covers before power supplying this device is
Replace all covers before power supplying this device is
turned on.
turned on.
8
TA6JG20 3VL9402-4TP01
3TA6JG20 3VL9402-4TP31
A
B
C
Wire Connector
60°C and 75°C
[ Conexión del
cable ]
[ Rango Cable ]
14 – 2 AWG
[ 2.5 – 35 mm² ]
TA6JG20
3TA6JG20
3VL9402-4TP01
1 – 2/0 AWG
3VL9402-4TP31
14 – 4 AWG
[ 2.5 – 16 mm² ]
TA12JG04
3TA12JG04
3VL9404-4TP01
[ 10 – 16 mm² ]
3VL9404-4TP31
Bestell-Nr. / Order No.: 3ZX1012-0VL68-2BA1
Technical Support:
Subject to change without prior notice
Siemens Industry, Inc. , Norcross, GA 30092 U.S.A.
Tensión peligrosa.
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Puede causar la muerte o lesiones graves.
Desenergice totalmente antes de instalar o darle servicio.
Desenergice totalmente antes de instalar o darle servicio.
Reemplace todas las barreras y cubiertas antes de
Reemplace todas las barreras y cubiertas antes de
energizar el interruptor.
energizar el interruptor.
3/16"
UL 486A - 486B
Wire Size
Req. Wire Stranding
( Cable )
CU / AL
Class
B
Cu / Al
7
Cu / Al
19
[ 50 mm² ]
Cu
7
Al
8 – 4 AWG
For Support in Europe refer to :
Internet: www.siemens.de/lowvoltage/technical-assistance
Toll Free: 1-800-241-4453
A
B
C
Torque
[ Esfuerzo de
torsión ]
CU
Class
C
6 – 2/0 AWG
[ 16 – 50 mm
2
]
19
120 lb. in. [ 14 Nm ]
8 AWG
[ 6 mm
2
]
40 lb. in [ 4.5 Nm ]
14 – 10 AWG
37
2
[ 2.5 - 4 mm
]
35 lb. in. [ 4 Nm ]
14 - 8 AWG
[ 2.5 – 6 mm
2
]
35 lb. in.
[ 4 Nm ]
19
6 - 4 AWG
[ 10 – 16mm
2
]
50 lb. in.
[ 5.6 Nm ]
3 / 3
Tension dangereuse.
Tension dangereuse.
Danger de mort ou risque de blessures graves.
Danger de mort ou risque de blessures graves.
Couper l'alimentation de l'appareil et barrer avant de
Couper l'alimentation de l'appareil et barrer avant de
travailler.
travailler.
Remplacez touts les couverts avant que
Remplacez touts les couverts avant que
l'approvisionnement de pouvoir soit alimenté.
l'approvisionnement de pouvoir soit alimenté.
TA12JG04
3VL9404-4TP01
3TA12JG04 3VL9404-4TP31
1/8"
Wire Strip Length
[ Quitar ]
B
A
.57 - .69
1.12 – 1.25
[ 15 – 17mm ]
[ 28 - 32mm ]
[ 32 - 35mm ]
.50 - .62
1.00 – 1.13
[ 13 – 15mm ]
[ 25 - 28mm ]
[ 41 - 44mm ]
GWA 4NEB 179 6941-10 DS 04
Internet: www.usa.siemens.com/powerdistribution
© Siemens Industry Inc. 2010
C
1.25 – 1.38
1.62 – 1.75
806941A03