ABB Sace Emax 2 Installation, Operation And Maintenance Instructions page 30

Emax e1.2 low voltage air circuit-breakers
Table of Contents

Advertisement

ABB | SACE Emax 2
Grounding The fixed part of withdrawable circuit-breakers has a screw for the earth connection.
The connection must be implemented by means of a conductor of suitable cross-section according to the
IEC 61439-1 Standard.
Clean and degrease the area around the screw before making the connection.
After assembly of the conductor, tighten the screw with a torque of 2 N m - 17.7 lb in.
Alternatively, no connection will be required if circuit-breaker frame continuity with the switchgear
earthing is provided by the metal contact (support) between the circuit-breaker and the metal structure
of the switchgear (or a part of the protection circuit) (as long as there are no insulating panels between
the circuit-breaker and the metal frame of the switchgear).
The fixed circuit-breaker version does not need an earth connection.
Figure 67
28 | © 2022 ABB | 1SDH000999R0002 - ECN000297030
Management operations