en | Installing
4.17

Connecting Analog Input Devices

The AMC2-4R4 has 8 analog inputs, for example, for potential-free lock mechanisms, or to
detect whether a lock is closed or open. The inputs will be connected to the 2-pin pluggable
screw connectors: S3, S4, S8, S9, S15, S16, S20 and S21 - refer to Connecting Diagrams, page
102.
The AMC2-4W has 8 analog inputs, for example, for potential-free lock mechanisms, or to
detect whether a lock is closed or open. The inputs will be connected to the 2-pin pluggable
screw connectors: S3, S4, S8, S9, S15, S16, S20 and S21 - refer to Connecting Diagrams, page
102.
The AMC2-8IOE has the connectors S2 - 5 and S10 - 13, only.
Notice!
Risk of damage to equipment
Do not connect external power supply to the AMC2 inputs.
When connecting a relay output to an AMC2 input use dry mode with potential-free contact -
refer to Connecting Relay Outputs, page 75.
Figure 4.75: Location of the analog input connectors
Figure 4.76: Location of the analog input connectors
2020-01 | V02 |
Installation manual
Access Modular Controller 2
Bosch Access Systems V.B.