ABB ACQ580-01 Quick Installation And Start-Up Manual page 12

Ul type 4x (ip66) drives, nec types
Table of Contents

Advertisement

ACQ580-
Nominal ratings
01-...
Input
Output
current
current
light duty
I
I
1
LD
A
A
02A7-6
2.7
2.7
03A9-6
3.9
3.9
06A1-6
6.1
6.1
09A0-6
9.0
9.0
011A-6
11.0
11.0
017A-6
17.0
17.0
022A-6
22
22
027A-6
27
27
032A-6
32
32
1) I
= Nominal current with 10% overload allowed for one minute every ten minutes.
Ld
2) P
= Typical motor power with no overload capacity. P
n
ratings apply to most NEMA 4-pole motors.
3) For IEC installations, ABB recommends aR fuses. See hardware manual for guidelines in selecting between aR and gG fuses, and for additional fuse alternatives.
4) When option +F254 is included (UL98 input disconnect switch with handle and fuses), the type JJS fuses as listed are included inside the drive. Otherwise, the recommended branch
protection fuses must be used externally to maintain the IEC/EN/UL 61800-5-1 and CSA C22.2 No. 274 certifications.
5) IEC 61439-1: The drive is suitable for use on a circuit capable of delivering not more than 65 kA when protected by the fuses given in this table.
6) UL 61800-5-1, CSA C22.2 No. 274: The drive is suitable for use on a circuit capable of delivering not more than 100,000 symmetrical Amperes (rms) at 600 V maximum when
protected by the ABB recommended fuses, internally or externally. Option +F254 (UL98 input disconnect switch with handle and internal fuses) provides branch circuit protection at this
100,000 A rating without the need for external upstream fuses.
7) Refer to
Alternate Fuses, MMPs and Circuit Breakers for ABB Drives (3AXD50000645015 [English])
protection.
8) Class J, CC, and CF fuses are also allowed at the same nominal current and voltage ratings as external fuses.
9) IEC Installations: The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top of the other, ambient temperature 30 °C, PVC
insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-52/2001). For other conditions, size the cables according to local safety regulations, appropriate input voltage and
the load current of the drive.
10) NEC Installations: The cable sizing is based on NEC Table 310-15 for copper wires, 75 °C (167 °F) wire insulation at 40 °C (104 °F) ambient temperature. Not more than three
current-carrying conductors in raceway or cable or earth (directly buried). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the
load current of the drive.
4)
Fuses
Motor
gG fuse
1)
2)
power
(IEC 60269)
P
P
ABB type
n
LD
kW
hp
1.5
2.0
-
2.2
3.0
-
4.0
5.0
-
5.5
7.5
-
7.5
10.0
-
11.0
15.0
-
15.0
20.0
-
18.5
25.0
-
22.0
30.0
-
= Typical motor power in light duty use (10% overload). The kilowatt ratings apply to most IEC 4-pole motors. The horsepower
Ld
Typical power cable sizes,
Cu
uR/aR
UL class
3)5)
6)7)8)
fuse
T
(DIN 43620)
Bussmann type
mm
-
JJS-15
-
-
JJS-15
-
-
JJS-15
-
-
JJS-15
-
-
JJS-15
-
-
JJS-30
-
-
JJS-40
-
-
JJS-40
-
-
JJS-40
-
for additional UL fuses and circuit breakers that can be used as branch circuit
Frame
size
2 9)
10)
AWG
14
R2
14
R2
14
R2
14
R2
14
R2
10
R2
10
R3
8
R3
8
R3
12