Motor Overload Protection; Fieldbus Communication; Warnings And Faults - ABB ACQ580-01 Quick Installation And Start-Up Manual

Table of Contents

Advertisement

Motor overload protection

The motor thermal overload protection is set to motor current and motor class curves as default. Motor thermal overload
protection can also be measured using motor temperature devices or can be estimated using a motor model defined by
parameters. To enable protection using motor model parameters or measurement devices set parameter 35.11 and
subsequent parameters through 35.55. To adjust motor class curves (default is class 20), change parameters 35.56 and
35.57.
?
Use the information key ( ) on the drive control panel for more information on setting group 35 parameters. You must set
the drive overload parameters correctly, or motor damage could occur.

Fieldbus communication

To configure the embedded fieldbus communication for Modbus RTU, you must set at least these parameters:
Parameter
20.01 Ext1 commands
22.11 Ext1 speed ref1
28.11 Ext1 frequency ref1
58.01 Protocol enable
58.03 Node address
58.04 Baud rate
58.05 Parity
58.06 Communication
control
Other parameters related to the fieldbus configuration:
58.14 Communication loss
action
58.15 Communication loss
mode
58.16 Communication loss
time

Warnings and faults

Warning Fault
Aux. code
A2A1
2281
Current calibration
A2B1
2310
Overcurrent
A2B3
2330
Earth leakage
A2B4
2340
Short circuit
-
3130
Input phase loss
-
3181
Wiring or earth fault
A3A1
3210
DC link overvoltage
A3A2
3220
DC link undervoltage
-
3381
Output phase loss
-
5090
STO hardware failure
A5A0
5091
Safe torque off
A7CE
6681
EFB comm loss
A7C1
7510
FBA A communication
A7AB
-
Extension I/O
configuration failure
Setting
Description
Embedded
Selects fieldbus as the source for the start and stop commands when
fieldbus
EXT1 is selected as the active control location.
EFB ref1
Selects a reference received through the embedded fieldbus interface
as speed reference 1. Use this parameter with the vector motor
control mode.
EFB ref1
Selects a reference received through the embedded fieldbus interface
as frequency reference 1. Use this parameter with the frequency motor
control mode.
Modbus RTU
Initializes embedded fieldbus communication.
1 (default)
Node address. There must be no two nodes with the same node
address online.
19.2 kbps (default) Defines the communication speed of the link. Use the same setting as
in the master station.
8 EVEN 1 (default)
Selects the parity and stop bit setting. Use the same setting as in the
master station.
Refresh settings
Validates any changed EFB configuration settings. Use this after
changing any parameters in group 58.
58.17 Transmit delay
58.25 Control profile
58.26 EFB ref1 type
Description
Warning: Current calibration is done at the next start.
Fault: Output phase current measurement fault.
The output current is more than the internal limit. This can also be caused by
an earth fault or phase loss.
A load unbalance that is typically caused by an earth fault in the motor or the
motor cable.
There is a short-circuit in the motor or the motor cable.
The intermediate DC circuit voltage oscillates due to missing input power
line phase.
Incorrect input and motor cable connection.
Intermediate DC circuit voltage is too high.
Intermediate DC circuit voltage is too low.
All three phases are not connected to the motor.
STO hardware diagnostics has detected hardware failure. Contact ABB.
The Safe torque off (STO) function is active.
Break in embedded fieldbus communication.
Communication lost between drive (or PLC) and fieldbus adapter.
The installed C-type module is not the same as configured, or there is an
error in the communication between the drive and module.
58.28 EFB act1 type
58.31 EFB act1 transparent
source
58.33 Addressing mode
58.34 Word order
58.101 Data I/O 1
...
58.114 Data I/O 14
12

Advertisement

Table of Contents
loading

Table of Contents