Hitachi HC-A32MB Installation And Operation Manual page 13

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 7
Installation
DIP switch setting
¡
Name
Function
SW1
Not available
SW2
Reset
SW3
Not available
(TELE)
SW4
Configuration
SW5
Configuration
SW6
Configuration
SW7
Options 2
SW8
Options 1
(Application type)
SW9
Not available
SW10
HC-A32MB address
SW11
H-LINK DSW
D4, D11
H-LINK
D7
Power
D9/D10
Not used
D12
MODBUS
D13
Operation
Factory setting
All in off (no function)
Reset button. To be used in case of program has been locked
Factory purposes. Never change it
Setting functions
Setting functions
Setting functions
SW7-1: 0FF-SLAVE / ON-MASTER. To be used in case of several HC-
A32MB in the same H-LINK. Only one HC-A32MB should be set as master.
SW7-2: OFF - EVENT CONTROL / ON - CHANGE CONTROL
SW7-3: OFF - Parity disabled / ON - Parity enabled
SW7-4: OFF - Even parity / ON - Odd parity
SW7-5: OFF - 19200 Bps / ON - 9600 Bps
SW7-(6~8): Not used
SW8-1: 0FF-PACKAGED / ON-CHILLER. To be set according units
application
SW8-2~8: Not used
All in off (no function)
HC-A32MB address from 1 to 32 by pins 1 to 5
2-Pins DSW
SW11-1: H-LINK end resistance
SW11-2: Not used
H-LINK transmission
Power supply ON/OFF
-
-
-
Modbus communication in RS485
-
Normal software operation
Description
PMML0191A rev.2 - 05/2013
11