Cycle alarms code list
¡
(ERROR_CODE_CYC: address 16~21)
Cycle alarm
7SEG1
7SEG2
Activation of High Pressure Switch


Activation of Low Pressure Control


Activation of Compressor Internal Thermostat

7
Activation of Discharge Gas Thermistor

6
Activation of Thermal Relay for Comrpressor or

5
Malfunction of Auxiliary Relay ARrn
Incorrect Setting of Fan Number

0
Activation of Fan Motor Internal Thermostat

4
Excessively Low Pressure


Excess Low Temperature of Cooler Inlet Refrigerant

9
Failure of Discharge Gas Pressure Sensor (open/short)

27
Failure of Suction Gas Pressure Sensor (open/short)

28
Failure of Water Outlet Temperature Thermistor

12
(for non single cycle unit)
Failure of Discharge GasThermistor (open/short)

23
Failure of Suction Gas Thermistor (open/short)

26
Phase Abnormally

05
Failure of Cooler Inlet Refrigerant Thermistor (Ope/Short)

21
Activation of Suction Gas Thermistor


Activation of Freeze Protection Control (for non single cycle unit)

13
Failure of Thermistor set before Expansion Valve (open/short)

24
Failure of Water Outlet Thermistor - Cooler Backside (open/short)

25
20
PMML0191A rev.2 - 05/2013
Description
Operation
HC-A32MB
value
1
2
3 - (A/W/CL)G(1)
9 - (A/W/CL)G2
4
5
6
7 - (A/W/CL)G(1)
3 - (A/W/CL)G2
8
10
11
12
14 - (A/W/CL)G(1)
24 - (A/W/CL)G2
15
16
17
19
20
21
23 - (A/W/CL)G(1)
13 - (A/W/CL)G2
24 - (A/W/CL)G(1)
14 - (A/W/CL)G2