PAC2000S12-B1 PSU
Parameter
Dip (HVDC)
Technical Manual
Conditions
Dip to 70% UT, hold-up time: 500 ms
Dip to 0% UT, hold-up time: 5000 ms
Dip to 40% UT
Hold-up time: 1 ms/3 ms/10 ms/30
ms/100 ms/300 ms/1000 ms
Dip to 70% UT
Hold-up time: 1 ms/3 ms/10 ms/30
ms/100 ms/300 ms/1000 ms
Dip to 0% UT
Hold-up time: 1 ms/3 ms/10 ms/30
ms/100 ms/300 ms/1000 ms
Dip to 80% UT
Hold-up time: 100 ms/300 ms/1000
ms/3000 ms/10000 ms
Dip to 120% UT
Hold-up time: 100 ms/300 ms/1000
ms/3000 ms/10000 ms
A EMC Specifications
Criterion
IEC 61000-4-11, criterion
B
IEC 61000-4-11, criterion
C
IEC 61000-4-11, criterion
B
IEC 61000-4-11, criterion
B
IEC 61000-4-11, criterion
B
IEC 61000-4-11, criterion
A
IEC 61000-4-11, criterion
A