PAC2000S12-B1 PSU
Parameter
Conducted emission (CE)
Radiated emission (RE)
Electrostatic discharge
(ESD)
Electrical fast transient
Radiated susceptibility (RS)
Conducted susceptibility
(CS)
Power magnetic
susceptibility (PMS)
Surge
Dip (AC)
Technical Manual
A
Conditions
Class A, 6 dB
Class A, 6 dB
Class A, 6 dB, 30 MHz to 1 GHz
Contact: ±6 kV, air: ±8 kV
Contact: ±8 kV, air: ±15 kV
±2 kV
10 V/m, 80 MHz to 6 GHz
10 V, 150 kHz to 80 MHz
30 A/m
AC input surge:
Differential mode: ±2.5 kV for L to N
(1.2/50 µs, 2 ohms)
Common mode: ±2.5 kV for L to PE, N
to PE, and L and N to PE (1.2/50 µs, 12
ohms)
HVDC input surge:
Differential mode: ±2 kV for P to N
(1.2/50 µs, 2 ohms)
Common mode: ±2 kV for P to PE, N to
PE, and P and N to PE (1.2/50 µs, 12
ohms)
Dip to 0% UT, hold-up time: 10 ms
(80% load of a single PSU)
Dip to 0% UT, hold-up time: 20 ms
(40% load of a single PSU)

A EMC Specifications

EMC Specifications
Criterion
EN 55032
EN 55032
FCC Part15
IEC 61000-4-2, criterion B
IEC 61000-4-2, criterion C
IEC 61000-4-4, criterion B
IEC 61000-4-3, criterion A
IEC 61000-4-6, criterion A
IEC 61000-4-8:2001,
criterion A
IEC 61000-4-5, criterion B
IEC 61000-4-5, criterion B
IEC 61000-4-11, criterion
A
IEC 61000-4-11, criterion
A
60