TP48200A-HT19C4-1 and TBC300A-TCA2 Telecom
Power
User Manual
Item
Specifications
DC output
Output voltage range
Default output voltage
Output power
Regulated voltage precision
Ripple and noise
Noise weighting
Imbalance of load sharing
AC input
AC input overvoltage protection threshold
protection
AC input overvoltage recovery threshold
AC input undervoltage protection threshold
AC input undervoltage recovery threshold
DC output
DC output overvoltage protection threshold
protection
AC surge
Level B surge protection; nominal surge discharge current: 30 kA (8/20 µs); maximum
protection
surge discharge current: 60 kA (8/20 µs)
DC surge
Differential mode: 10 kA (8/20 µs); common mode: 20 kA (8/20 µs)
protection
Safety and
Complies with the IEC/EN60950-1.
regulatory design
MTBF
200,000 hours
A.3 EMC Specifications
Table A-3 EMC specifications
Item
Electromagnetic
interference (EMI)
Issue 03 (2019-11-15)
Specifications
Conducted emission (CE)
Copyright © Huawei Technologies Co., Ltd.
AC, 50%-100% load)
-42 V DC to -58 V DC
-53.5 V DC
The maximum output power is the number
of rectifiers multiplied by the output power
of a single rectifier.
≤ ±1%
≤ 200 mVp-p
≤ 2 mV
< ± 5% (20%-100% load percentage)
> 300 V AC
When the voltage is restored to 290 V AC,
the output resumes.
< 85 V AC
When the voltage is restored to 90 V AC,
the output resumes.
Range: -58.5 V DC to -60.5 V DC
1. If an overvoltage occurs inside a
rectifier, the rectifier locks out.
2. If the external voltage is above –63 V
for more than 500 ms, the rectifier locks
out.
EN55022
AC power port: Class B
A Technical Specifications