A.1 Environmental Specifications
Table A-1 Environmental specifications
Item
Operating temperature
Transportation temperature
Storage temperature
Operating humidity
Storage humidity
Altitude
Noise level
A.2 Electrical Specifications
Table A-2 Electrical Specifications
Item
Specifications
AC input
AC input system
AC input voltage
Input frequency
Power factor
Total harmonic distortion (THD)
Issue 03 (2019-11-15)
A
Technical Specifications
Specifications
-10° C to +45° C
-40° C to +70° C
-40° C to +70° C
5%-95% RH
5%-95% RH
0-4000 m
When the altitude ranges from 2000 m to 4000 m, the operating
temperature decreases by 1° C for each additional 200 m.
Complies with GR487. Acoustic pressure level: <65dBA@1.5 m
Copyright © Huawei Technologies Co., Ltd.

A Technical Specifications

110 V AC dual-live wire
85 V AC-300 V AC
Frequency range: 45-66 Hz; nominal
frequency: 50 Hz or 60 Hz
≥ 0.99 (rated input and load)
≤ 5% (Vin = 208 V AC, 220 V AC, 230 V
77