Electrical Connections - ABB SM2000 User Manual

Advanced videographic recorder
Hide thumbs Also See for SM2000:
Table of Contents

Advertisement

...5 INSTALLATION
5.3 Electrical Connections – Fig 5.5
Module Positions
A
B
C
D
Positions A and B
Analog Inputs
Section 5.4
+
THC
mA
1
V, mV
RTD
2
3
+
THC
mA
4
V, mV
RTD
5
6
+
THC mA
7
V, mV
RTD
8
9
10
11
+
THC mA
12
V, mV
RTD
13
14
+
THC mA
15
V, mV
RTD
16
17
+
THC mA
18
RTD
V, mV
19
20
Note.
An external voltage divider (part no. GR2000/0375) is required for each channel on which 'Input type' is set to 'Voltage'
– see Sections 4.6.2 and 5.4.1.
74
Information.
• Always route signal leads and power cables separately, preferably in earthed
E
metal conduit.
• It is strongly recommended that, for signal inputs and relay connections,
screened cable is used, with the screen connected to the earth stud.
F
• The terminals accept cables up to 2.5mm
*Note. An external divider (part no. GR2000/0375) is
required for each channel for voltage input ranges above 2V
Positions C and D
Positions C and D
Relays
24V PSUs
Section 5.7
Section 5.4.4
NC
1
1
2
2
NO
3
C
3
NC
4
4
5
NO
5
6
C
6
NC
7
7
8
NO
8
C
9
9
10
10
NC
11
11
12
NO
12
13
C
13
14
NC
14
15
15
NO
16
16
C
NC
17
17
18
18
NO
19
19
C
20
20
Fig 5.5 Electrical Connections
2
cross-section.
Position C
Positions C and D
Ethernet
+
24V
Transmit
45mA
LED
Continuity/
receive LED
+
24V
45mA
RJ45
Connector
+
Position E
Power Supplies
Hybrid Board
Sections 5.4.4 & 5.6
Section 5.8
di1
1
2
di2
3
di3
Digital
4
di4
Inputs
5
di5
Section
6
di6
5.8.2
7
COM
8
COM
9
do1
10
do2
Digital
11
do3
Outputs
Section
12
do4
5.8.1
13
do5
14
do6
15
COM
COM
16
+
17
Analog
a01
18
Outputs
+
19
Section
a02
5.8.3
20
L
1
2
N
3
+
4
24V DC
5
6
+
7
Tx PSU
8
Position F
RS 485
Section 5.5
1
2
3
4
+
Tx
5
+
6
Tx/Rx
7
COM
8

Advertisement

Table of Contents
loading

Table of Contents