Mitsubishi Electric CMB-WM108V-AA Service Handbook page 183

Hide thumbs Also See for CMB-WM108V-AA:
Table of Contents

Advertisement

[ VIII Troubleshooting ]
Troubleshooting according to the remote controller malfunction or the external input error
In case of ME remote controller
In case of ME remote controller
1. Phenomena
Even if the operation button on the remote controller is pressed, the display remains unlit and the unit does not start running.
(Power indicator
does not appear on the screen.)
(1) Cause
1) The power for the M-NET transmission line is not supplied from the indoor unit.
2) Short circuit of the transmission line.
3) Incorrect wiring of the M-NET transmission line on the outdoor unit.
Disconnected wire for the MA remote controller or disconnected line to the terminal block.
The indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7).
4) Disconnected transmission line on the remote controller.
5) Remote controller failure
6) Outdoor unit failure
(2) Check method and remedy
1) Check voltage of the transmission terminal block for of the ME remote controller.
If voltage between is 17V and 30V -> ME remote controller failure
 When voltage is 17V or less -> Refer to VIII [4] -3- (2) "Troubleshooting transmission power curcuit of outdoor
unit".(page 195)
2) When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.
HWE1708A
- 174 -
GB

Advertisement

Table of Contents
loading

Table of Contents