[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor
unit (OC), of the terminal block for indoor-outdoor trans-
mission line (TB02) on the main and sub HBC controllers
(HB and HS), and of the terminal block for indoor-outdoor
transmission line (TB5) on each indoor unit (IC). (Non-
polarized two-wire)
Only use shielded cables.
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor unit
(OC), the S terminal of the terminal block (TB02) on the
HB and HS, and the S terminal of the terminal block
(TB5) on the indoor unit (IC) with the shield of the shield-
ed cable.
2) Transmission line for centralized control
Daisy-chain terminals A and B of the system controller,
M1 and M2 terminals of TB7 (terminal block for central-
ized control system connection) on the outdoor units
(OC) in different refrigerant systems, and M1 and M2 ter-
minals of TB7 (terminal block for centralized control sys-
tem connection) on the outdoor unit (OC) in the same
refrigerant circuit.
If a power supply unit is not connected to the transmis-
sion line for centralized control, replace the power jump-
er connector on the control board from CN41 to CN40 on
only one of the outdoor units.
When connecting a system controller, set the centralized
control switch (SW5-1) on the control board of all indoor
units to "ON."
a) When connecting TB7, only commence after checking
HWE1708A
that the voltage is below 20 VDC.
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal of the terminal block (TB7) on
the system controller, OC with the shield of the shielded
cable. Short-circuit the earth terminal (
minal on the terminal block (TB7) on the outdoor unit
whose power jumper connector is mated with CN40.
3) MA remote controller wiring
Same as [7] -1-
When 2 remote controllers are connected to the sys-
tem
Same as [7] -1-
Group operation of indoor units
Same as [7] -1-
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals
on the terminal block for indoor-outdoor transmission line
(TB5) on LOSSNAY (LC). (Non-polarized two-wire)
Indoor units must be interlocked with the LOSSNAY unit
using the system controller. (Refer to the operation man-
ual for the system controller for the setting method.) In-
terlock setting from the remote controller is required if the
ON/OFF remote controller alone or the LM adapter alone
is connected.
5) Switch setting
Address setting is required as follows.
- 50 -
) and the S ter-
GB