CONTROL WIRING

Control Wire Drawing
Outdoor
P Q
Communication wire between
indoor & outdoor without polarity
Indoor 1
Indoor 4
Indoor 7
Wired Controller ABC Chart
Length of Controller Wire ft (m)
≤820(250)
The shielding layer of the controller wire must be grounded at the outdoor unit chassis ground.
The total length of the controller wire shall not be more than 820ft(250m)
26
Indoor 2
A B C
P Q
P Q A B C
Indoor 5
P Q A B C
P Q A B C
A B C
Wired controller
Indoor 8
P Q A B C
A B C
Wired controller
Wiring Dimensions AWG (mm2)
18(0.75) x 3 core shielding line
Control wire for wired controller with polarity
Indoor 3
P Q A B C
Indoor 6
P Q A B C
A B C
Wired controller
Indoor 9
P Q A B C
P Q A B C
A B C
Wired controller
Wired controller Wired controller
A B C
Wired controller
A B C
Wired controller
A B C
A B C
31-5000755 Rev. 0