Advertisement

Chapter 3
Location of
Receptacles
for Jumper
Cables for
a Typical
Rack
Note PDU
Vertically
Mounted
with
Receptacles
Facing
Inward
Figure 3-4. Power Connection Locations on a Typical Rack (Rear View)

208V PDU Rack Power Configurations

The 208 VAC PDU power configurations appear as shown below in Table
and Figure 3-5.
3-1
Recommended 208 VAC Power Configurations
In the United States, if you are using a UPS, then use PDU model E7671A or
E7672A. Attach the IEC 320 C-19 end of the E7801A cord to the PDU and attach
the L6-20 end of the same cord to the NEMA L6-20 receptacle on the UPS.
34
Procedure for Connecting and Routing Cables to the LXr 8500
Monitor
HP Console Switch
DLT Library
Mass Storage Unit
(Two Inlets)
HP NetServer
LXr 8500
Mass Storage Unit
(Two Inlets)