Download Print this page

Technical Data - Panasonic EBL128 4550 Overview

Fire alarm system

Advertisement

4550
EBL128 c.i.e. (128 addresses). Batteries are not included.
4552
RS485 transceiver component, for up to four display units, i.e. Ext. Fire Brigade
Panels 1826 / 1828, Ext. Presentation Unit 1728 and/or Alert Annunciation Units
1735 / 1736.
4551
Expansion board holder. (For two 4580 and two 4581 expansion boards.)
4580
8 zones expansion board.
4581
8 relays expansion board.
4513
Cabinet for drawings. (Similar to the EBL128 cabinet.)
The 4580 board can be used to connect conventional detectors and manual call points to
EBL128. An end-of-line capacitor (470 nF) shall be connected in the last alarm point on each
zone line.
More information is available in the EBL128 Planning Instructions & Operating Instructions.
Voltage
primary (V AC)
secondary (V DC)
normal
by battery backup
Current consumption (mA)
Ambient temperature (C)
Operating
storage
Ambient humidity (% RH)
Ingress Protection rating (estimated)
Inputs
Outputs
Interfaces
Size H x W x D (mm)
Weight (kg)
Colour (metal cabinet)
Approvals
Note! All voltages are nominal. For more information see EBL128 Planning Instructions MEW00508.
1
Relay contacts: max. 1 A @ 30 V DC.
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
MEW00503
Type numbers

Technical data

230
24
21 - 30
Depending on connected units, etc. See EBL128 Planning Instructions.
-5 to +40
-40 to +75
max. 95, non condensing
IP32
1 COM loop for 128 addresses
1 programmable input. NO / NC (R>2K = open circuit). Max. 2 mA.
Alt. supervised, normally high resistance (3K3) or low (680R).
1 programmable supervised voltage output (24 V DC, max. 500 mA)
1 programmable supervised voltage output (24 V DC, max. 200 mA)
1 programmable relay output.
brigade tx).
1 non-programmable relay output.
Power supply (24 V DC, max. 200 mA) for routing equipment
Power supply (24 V DC, max. 500 mA) for external equipment (Web-
server, up to 4 ext. FBPs, etc.) Web-server requires approx. 65 mA.
RS232 ("D" connector) for a PC (Win128)
RS232 for a Web-server 1598
Socket for an optional RS485 transceiver, for ext. FBPs, EPUs and/or
AAUs.
511 x 416 x 123
12.2 (Excl. Batteries)
Aluminium & light grey (NCS S1500-N, PMS Cool Grey 2)
EC certificate no. 0786-CPD-20971
EN54-2:1997 / A1:2006, EN54-4:1997 / A2:2006
The Swedish front conforms to SS3654.
Date of issue
2006-04-04
1
Default set for routing equipment (Fire
1
For routing equipment (Fault tx).
Revision / Date of revision
4 / 2010-09-30

Advertisement