Activate / Deactivate Interlocking Output (H9/C2); Disable / Re-Enable Interlocking Output (H9/C3); Technical Manual Ft1020G3 Rev; Interlocking Control Expressions - Panasonic Firetracker FT1020G3 CIE Technical And Programming Manual

Hide thumbs Also See for Firetracker FT1020G3 CIE:
Table of Contents

Advertisement

PP = Interlocking combination Point within the Area
Date (dd-mm-yyyy) and time (hh:mm).
Use "↑" "↓" to scroll between several interlocking combinations.
15.3.2

Activate / deactivate interlocking output (H9/C2)

Activate
Even if the control expression for an interlocking output is not fulfilled (true), the output can
be manually activated via this menu.
The "Interlocking Combination" (Area / Point) is to be entered to activate the output. The
corresponding interlocking input will be "monitored" in the same way as if the output was
activated by its control expression.
Deactivate
Activated interlocking outputs are listed here. Use "↑" "↓" to scroll between the "Interlocking
Combinations" (Area / Point).
Interlocking output activated via its control expression and latched output selected: The
output has to be reset via this menu.
Interlocking output activated via its control expression and latched output not selected: The
output can be reset via this menu.
Interlocking output activated via this menu: The output has to be reset via this menu.
15.3.3

Disable / re-enable interlocking output (H9/C3)

Disable
Interlocking outputs (i.e. Output Type = Interlocking) can be individually disabled via this
menu (Not via menu H2/B2). A disabled output will stay in (or return to) the normal
condition for the output respectively. The "Interlocking Combination" (i.e. Area / Point) is to
be entered to disable the output.
All the interlocking outputs in the system can be disabled / re-enabled collectively via menu
H2/B3.
Re-enable
Interlocking outputs (i.e. Output Type = Interlocking) can be re-enabled via this menu (Not
via menu H2/B2).
Disabled interlocking outputs are listed in this menu. Use "↑" "↓" to scroll between the
"Interlocking Combinations" (i.e. Area / Point) or type it via the key-pad.
15.4

Interlocking control expressions

A programmable output control expression can contain "interlocking" trigger conditions
("Functions") numbers 22-25 (see chapter "Control expression", page 86), i.e. one or more
outputs can be activated when one or more interlocking inputs are activated.
Technical/Programming Manual
100
FT1020G3 Rev 2.2.1