Activate Interlocking Output (H9/C2) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
31.2
Action
"Access"
Scroll to menu H9.
"A"
Scroll to menu C2.
"A"
Write the area and point,
e.g.:
"A"
Rev: 1

Activate interlocking output (H9/C2)

The output in each interlocking combination (area / point) can be
manually activated via this menu. The corresponding interlocking
input will be "monitored" in the same way as if the output was
activated by its control expression.
Reset has to be performed via menu H9/C3.
(In the Chinese convention, the LED "Output" is indicating one or
more activated interlocking outputs.)
Text in display
Interlocking outputs and inputs
Activated interlocking outputs/inputs
Activate interlocking output
Activate interlocking output
area 000 point 00
Activate interlocking output
area 001 point 01
Activate interlocking output
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? H9
ACCEPT? C1
ACCEPT? C2
ACCEPT?
ACCEPT?
ACCEPT? C2
134
Comments
According to chapter
"Access", see page 72.
Press "A" to accept and/or
"Return" to menu C2.
Scroll or press "Return" to
menu H9. Scroll or press
"Return" to log off.