Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
24.2
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B2.
"A"
Write zone number and
address
(e.g. 001 / 01)
"A"
"A"
Rev: 1

Disable zone / address (H2/B2)

Addressable alarm points (also addressable manual call points),
connected to the COM loop, can be individually disabled.
Disabled alarm points, zone / addresses, are listed in menu H4/U1
from which it is also possible to get a print-out.
Disabled alarm points, zone / addresses, have to be re-enabled via
menu H4/B2.
Text in display
Disable or re-enable
Disable zone
Disable zone / address
Disable zone: 000 Address: 00
Disable zone: 001 Address: 01
Automatic re-enabling:0 (0=No,1=Yes)
Time: HH:MM
(Default is current time + 3 hours)
Disable zone: 000 Address: 00
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B2
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
77
Comments
According to chapter
"Access", see page 72.
Press "A" to accept.
Press "1" for aut. re-
enabling and accept or
change the time (max. 24
hours). Press "A" to
accept. LED
"Disablements" (L8) will
light up.
If more disablements
shall be done, continue
like above. If not, press
"Return" to menu B2.
Scroll or press "Return"
to menu H2. Scroll or
press "Return" to log off.