Disable / Re-Enable Alarm Devices (H2/B9) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
24.9
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B9:
"A"
"A"
Rev: 1

Disable / Re-enable alarm devices (H2/B9)

73
Outputs
programmed as type 3 = alarm device (sounder) can be
disabled all at the same time. Disabled alarm devices means that
even if the control expression (trigger condition) for output
respectively is fulfilled, the output will not be activated.
Disabled alarm devices are indicated by LED Fault / Disablements
"Alarm devices" (L13) and LED "Disablements" (L8) and is also
shown in menu H4/U1.
The outputs in one or more control units can be disabled or the outputs
in all control units.
The outputs will be disabled until re-enabled again (via this menu).
NOTE! This function is not the same as push button "Silence alarm
devices" (P3), see chapter ""Silence Alarm devices"", page 25. This
function has higher priority than "Silence alarm devices".
Text in display
Disable or re-enable
Disable zone
Disable / Re-enable alarm devices
Disable (=0) or Re-enable (=1) alarm
devices? 1
CU 99 (99 = All)
Disable / Re-enable alarm devices
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B9
ACCEPT?
ACCEPT? B9
86
Comments
According to chapter
"Access", see page 72.
Press "1" or "0", write the
CU number (or "99" for all
75
CUs)
and press "A" to
accept.
Scroll or press "Return" to
menu H2. Scroll or press
"Return" to log off.