Operating Instructions Fire alarm system EBL512 V2.3.x

Disable or re-enable (H2)

A whole zone, one or more alarm points within a zone and/or control
outputs can be disabled via menus H2/B1-B3. This possibility can be
used when a temporary disablement is wanted (e.g. craftsmen working
in the premises, etc.).
The function Enhanced disablement is enabled as default i.e.
disabled alarm points will not activate Pre-warning, fire alarm or fault.
If this function is not enabled (via Win512), fault can be activated but
not pre-warning or fire alarm. (This is a violation to the EN54-2
standard.
Addressable manual call points can be disabled (but shall normally not
be disabled).
However, when a whole zone is disabled, the
addressable manual call points will not be disabled for safety reasons.
Up to 512 whole zones can be disabled via menu H2/B1.
Up to 200 alarm points (zones / address) can be individually
disabled via menu H2/B2 and/or COM / BS4 loops, zone interface
inputs and/or MIO inputs can be disabled via menu H8/S2. (Alarm
points disabled via time channels are not limited and must not be
counted!)
Up to 200 outputs can be individually disabled via menu H2/B3.
Disabled output will stay in (or return to) the normal condition for the
output respectively. (Disabled outputs via menu H2/B8 and menu
H2/B9 are not limited and must not be counted!)
Up to 200 Interlocking outputs can be individually disabled via
menu H9/C4. (All interlocking outputs disabled via "000/00" are not
limited and must not be counted!)
It is not possible to exceed the limits. A warning will be shown:
Max. disablements reached!
Disablement not performed.
Don't forget to re-enable (via menus H2/B4-B6, B8 or B9, H8/S3,
H9/C5 or use automatic re-enablement for zones and alarm points.
Disablements are indicated by LED "Disablements" (L8) and are also
72
shown in the display
Zone 001 is disabled
More... is indicating two or more disablements.
Disablements (and faults) are indicated by a 2-sec. beep when an open
control unit door is being closed.
72
NOTE! See chapter "Alphanumeric display in the control unit", page 20
regarding priority order.
75
. An example:
ACCEPT?
More...