Test Alarm Devices (H8/S7) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
30.8
Action
"Access"
Scroll to menu S7.
"A"
"A"
Rev: 1

Test alarm devices (H8/S7)

The programmable outputs
activated via this menu (H8/S7), which make it possible to test the
alarm devices.
The test can not be started if fire alarm is activated in the system.
One or all control units can be selected. When the test starts the alarm
devices will sound for approx. 5 seconds, be silent for approx. 25
seconds, sound for approx. 5 seconds and so on.
NOTE! Also disabled (and silenced) alarm devices will be tested.
The test will continue for one hour, is stopped via this menu (H8/S7)
or if a fire alarm is activated in the system.
Text in display
Test alarm devices
Test alarm devices on CU 00? (99 = All)
Test alarm devices
91
Including Addressable siren 3377 and Addressable sounder base 3378.
92
The output activation will be continuously (steady). For the alarm devices
3377 and 3378, the tone with the highest priority level (and type "alarm
device") will be automatically selected.
Operating Instructions Fire alarm system EBL512 V2.3.x
91
type "Alarm device" can be collectively
ACCEPT?
ACCEPT?
ACCEPT?
126
92
Comments
According to chapter
"Access code for
maintenance", see page
119.
S7
Write a CU no. (or "99"
for all CUs) and press "A"
to accept.
Scroll or press "Return" to
return to menu H8. Scroll
S7
or press "Return" to log
off.